8.3 Connecting Peripheral Devices

8.3
Connecting Peripheral Devices
Figure 8.1
illustrates how to configure the drive and motor to operate with various peripheral devices.
• For more detailed instructions on how to install each device shown below, refer to the specific manual for that device.
Figure 8.1
Power
Supply
Line
Breaker
(MCCB)
and/or
Leakage
Breaker
Magnetic
Contactor
(MC)
AC Reactor
Zero-phase
Reactor
Fuse
Input Side
Noise Filter
<1> Terminals +1 and +2 for connecting a DC choke are available only in units CIMR-A 2A0004 to 0081 and CIMR-
A 40002 to 0044. Drives above have built in DC chokes.
<2> Terminals B1 and B2 for connecting a braking resistor are available only in units CIMR-A 2A0004 to 0138 and
CIMR-A 40002 to 0072.
<3> When using an external braking chopper in drives from CIMR-A 2A0004 to 0138 and CIMR-A 40002 to 0072
connect the chopper to drive terminals B1 and -. When using larger drives connect the chopper to terminals +3 and -.
376
LED Operator/LCD Operator
Drive
+2
+1
DC Reactor
<1>
Ground
R/L1 S/L2
T/L3
U/T1V/T2W/T3
24 V control
power supply
unit
Figure 8.1 Connecting Peripheral Devices
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
USB Cable
USB Copy unit
(Type-AB)
PC
USB Cable
(Type-AB, sold separately)
<2>
B1 B2
Thermal Relay
Braking Resistor
or
Braking Resistor Unit
Output Side
Noise Filter
Motor
Magnetic
Zero-phase
Contactor
Reactor
(switches to
line power)
Ground
Engineering Software Tools
DriveWizard
DriveWorksEZ
<3>
+3(B1)
Braking Unit
YEG