RS-422 Interface
Figure C.4
Note: 1. Turn on the DIP switch on the drive that is located at the end of the network. All other slave devices must have this DIP switch set to
the OFF position.
2. Set H5-07 to "0" when using the RS-485 interface.

◆ Network Termination

The two ends of the MEMOBUS/Modbus network line have to be terminated. The drive has a built in termination
resistor that can be enabled or disabled using DIP switch S2. If a drive is located at the end of a network line, enable the
termination resistor by setting DIP switch S2 to the ON position. Disable the termination resistor on all slaves that are not
located at the network line end.
Refer to
MEMOBUS/Modbus Termination on page 80
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
R –
S –
Drive
R+
S+
PLC
S –
R –
S2
S+
R+
IG
IG
OFF
S –
Drive
S+
R –
S2
R+
IG
OFF
S –
Drive
S+
R –
S2
R+
ON
IG
Figure C.4 RS-422 Interface
for details on setting S2.
C.3 Connecting to a Network
common_
TMonly
C
481