YASKAWA A1000 Series Technical Manual page 333

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

Digital Operator Display
Cause
Failed while attempting to read parameter settings from the
drive.
Digital Operator Display
Cause
Displayed while the parameter settings are being read onto
the USB Copy Unit.
Digital Operator Display
Cause
The drive the parameters were copied from and the drive
you performing the Verify mode on have different electrical
specifications or are a different capacity.
Digital Operator Display
Cause
Indicates that parameter settings that have been Read and
loaded onto the Copy Unit or Digital Operator are different.
Digital Operator Display
Cause
The Verify mode has confirmed that parameters settings on
the drive and parameters read to the copy device are
identical.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
rdEr
Error Reading Data
Press and hold the READ key on the USB Copy Unit for at least one second to have the unit read parameters from the
drive.
rEAd
Reading Parameter Settings (flashing)
Not an error.
vAEr
Voltage Class, Capacity Mismatch
Make sure electrical specifications and capacities are the same for both drives.
Parameter settings in the drive and those saved to the copy function are not the same
vFyE
To have parameters be the same, either write the parameters save on the USB Copy Unit or LCD digital operator onto
the drive, or Read the parameter settings on the drive onto the USB Copy Unit.
vrFy
Comparing Parameter Settings (flashing)
Not an error.
6.8 Copy Function Related Displays
Task
Possible Solutions
Task
Possible Solutions
Task
Possible Solutions
Task
Possible Solutions
Task
Possible Solutions
6
333