B.3 Parameter Table

B.3 Parameter Table

◆ A: Initialization Parameters

The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
A1: Initialization Parameters
No.(Addr.)
Name
A1-00
(100H)
Language Selection
<3>
A1-01
(101H)
Access Level Selection
<2>
A1-02
(102H)
Control Method Selection
<3>
A1-03
Initialize Parameters
(103H)
A1-04
Password
(104H)
A1-05
Password Setting
(105H)
A1-06
Application Preset
(127H)
A1-07
DriveWorksEZ Function Selection 0: DWEZ disabled
(128H)
<2> Default setting value is dependent on the Application Preset selected with parameter A1-06.
<3> Parameter setting value is not reset to the default value when the drive is initialized.
A2: User Parameters
No.(Addr.)
Name
A2-01 to
A2-32
User Parameters 1 to 32
(106 to 125H)
A2-33
User Parameter Automatic
(126H)
Selection
<1> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 does not equal 0.
<2> Default setting value is determined by the Application Preset selected with parameter A1-06.
400
All Modes
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
All Modes
0: View and set A1-01 and A1-04. U -
1: User Parameters (access to a set of parameters selected by the user, A2-01 to A2-32)
2: Advanced Access (access to view and set all parameters)
All Modes
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
All Modes
0: No initialization
1110: User Initialize (parameter values must be stored using parameter o2-03)
2220: 2-wire initialization
3330: 3-wire initialization
5550: oPE04 error reset
All Modes
When the value set into A1-04 does not match the value set into A1-05, parameters A1-01
through A1-03, A1-06, and A2-01 through A2-33 cannot be changed.
All Modes
0: General-purpose
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
6: Elevator
7: Hoist
All Modes
1: DWEZ enabled
2: Digital input (enabled when H1-
All Modes
Parameters that were recently edited are listed here. The user can also select parameters to
appear here for quick access.
All Modes
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters.
1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-
17 through A2-32 for quick access.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Description
parameters can also be viewed.
= 9F)
Description
Setting
common_
TMonly
Default: 0
Min: 0
Max: 7
common_
TMonly
Default: 2
Min: 0
Max: 2
common_
TMonly
Default: 0
Min: 0
Max: 7
common_
TMonly
Default: 0
Min: 0
Max: 5550
common_
Default: 0000
TMonly
Min: 0000
Max: 9999
common_
TMonly
Default: 0
Min: 0
Max: 7
common_
TMonly
Default: 0
Min: 0
Max: 2
Setting
common_
Default:
<2>
TMonly
Min: b1-01
Max: o2-08
common_
TMonly
Default: 1
<1>
Min: 0
Max: 1
Page
130
130
130
131
132
134
134
Page
135
135