YASKAWA A1000 Series Technical Manual page 450

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

B.3 Parameter Table
No. (Addr.)
Name
U2-19
Rotor Deviation at Previous
(7ECH)
Fault
U2-20
Heatsink Temperature at
(8EH)
Previous Fault
<19> This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01. The value will
have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer to
and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW.
<50> When reading the value of this monitor via MEMOBUS/Modbus a value of 8192 is equal to 100% of the drive rated output current.
U3: Fault History
No. (Addr.)
Name
U3-01 to
U3-04
(90H to 93H
First to 4th Most Recent Fault
(800H to
803H))
U3-05 to
U3-10
5th to 10th Most Recent Fault
(804H to
809H)
U3-11 to
U3-14
Cumulative Operation Time at
(94H to 97H
1st to 4th Most Recent Fault
(80AH to
80DH))
U3-15 to
U3-20
Cumulative Operation Time at
(80EH to
5th to 10th Most Recent Fault
813H)
U4: Maintenance Monitors
No. (Addr.)
Name
U4-01
Cumulative Operation Time
(4CH)
U4-02
Number of Run Commands
(75H)
U4-03
Cooling Fan Operation Time
(67H)
U4-04
Cooling Fan Maintenance
(7EH)
U4-05
Capacitor Maintenance
(7CH)
U4-06
Soft Charge Bypass Relay
(7D6H)
Maintenance
U4-07
IGBT Maintenance
(7D7H)
U4-08
Heatsink Temperature
(68H)
U4-09
LED Check
(5EH)
450
V/f
V/f w/PG
OLV/PM
AOLV/PM
Displays the degree of rotor deviation when the most recent fault occurred (same status will
appear as shown in U6-10).
All Modes
Displays the temperature of the heatsink when the most recent fault occurred.
All Modes
Displays the first to the fourth most recent faults.
All Modes
Displays the fifth to the tenth most recent faults.
After ten faults have occurred in the drive, data for the oldest fault is deleted. The most recent
fault appears in U3-01, with the next most recent fault appearing in U3-02. The data is moved to
the next monitor parameter every time a fault occurs.
All Modes
Displays the cumulative operation time when the first to the fourth most recent faults occurred.
All Modes
Displays the cumulative operation time when the fifth to the tenth most recent faults occurred.
All Modes
Displays the cumulative operation time of the drive. The value for the cumulative operation
time counter can be reset in parameter o4-01. Use parameter o4-02 to determine if the operation
time should start as soon as the power is switched on or only while the Run command is present.
The maximum number displayed is 99999, after which the value is reset to 0.
All Modes
Displays the number of times the Run command is entered. Reset the number of Run commands
using parameter o4-13. This value will reset to 0 and start counting again after reaching 65535.
All Modes
Displays the cumulative operation time of the cooling fan. The default value for the fan
operation time is reset in parameter o4-03. This value will reset to 0 and start counting again
after reaching 99999.
All Modes
Displays main cooling fan usage time in as a percentage of its expected performance life.
Parameter o4-03 can be used to reset this monitor.
All Modes
Displays main circuit capacitor usage time in as a percentage of their expected performance life.
Parameter o4-05 can be used to reset this monitor.
All Modes
Displays the soft charge bypass relay maintenance time as a percentage of its estimated
performance life. Parameter o4-07 can be used to reset this monitor.
All Modes
Displays IGBT usage time as a percentage of the expected performance life. Parameter o4-09
can be used to reset this monitor.
All Modes
Displays the heatsink temperature.
All Modes
Lights all segments of the LED to verify that the display is working properly.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Description
OLV
CLV
CLV/PM
Description
Description
Analog Output
Unit
Level
common_
TMonly
No signal output
0.1 deg
available
common_
No signal output
TMonly
1°C
available
Table A.2
and
Table
Analog Output
Unit
Level
common_
No signal output
TMonly
available
common_
TMonly
No signal output
available
common_
No signal output
TMonly
1 h
available
common_
No signal output
TMonly
1 h
available
Analog Output
Unit
Level
common_
TMonly
No signal output
1 h
available
common_
TMonly
No signal output
1 Time
available
common_
TMonly
No signal output
1 h
available
common_
TMonly
No signal output
1%
available
common_
TMonly
No signal output
1%
available
common_
TMonly
No signal output
1%
available
common_
TMonly
No signal output
1%
available
common_
TMonly
10 V: 100°C
1°C
common_
No signal output
TMonly
available
Page
A.3)
Page
Page

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents