Connect control wires as shown in the following figure:
Figure 3.29
To disconnect control wires from the terminals use the procedure described in
enters the terminal with a pair of pliers, then use a straight-edge screw driver to release the terminal and pull the wire out.
If it fits tightly, e.g. if ferrules are used, turn the wire for about 45° and then pull it gently out. Use this procedure to
remove the wire jumper between terminals HC, H1 and H2 that is preinstalled at shipping.
Figure 3.30
When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires (treating
wire ends as shown in
Figure 3.27
Figure 3.31
A – Drive side
B – Connect shield to ground terminal of
drive.
C – Insulation
NOTICE: The signal lines between the drive and the operator station or peripheral equipment should not exceed 50 meters when
using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system
performance.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Control Wires
Terminal Board
YEG
Figure 3.25 Terminal Board Wiring Guide
Push down to open
the terminal
Control Wires
Terminal Board
Figure 3.26 Removing Wires from the Terminal Board
and connect the shield to the ground terminal of the drive.
A
B
Figure 3.27 Preparing the Ends of Shielded Cables
Push wire end
into terminal
Figure
Turn the wire ~ 45
and pull it out of the
terminal.
Use a screwdriver with a blade
width of max 2.5 mm and a
thickness of max 0.4 mm
F
C
D
E
D – Control device side
E – Shield sheath (insulate with tape)
F – Shield
3.9 Control Circuit Wiring
3.26. Grasp the wire where it
YEG
3
75