YASKAWA A1000 Series Technical Manual page 512

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

D.2 European Standards
Three-Phase 200 V / 400 V Class
Figure D.4
Ground plate
(scrape off any visible paint)
A – Ground the cable shield
B – Enclosure panel
C – Metal plate
D – Grounding surface (remove any paint or sealant)
E – Drive
F – Motor cable (braided shield cable, max. 10 m)
Figure D.4 EMC Filter and Drive Installation for CE Compliance (Three-Phase 200 V / 400 V Class)
512
L3
L2
L1
L3 L2 L1
L3 L2
L3
L2 L1
L1
EMC noise filter
Make sure the ground wire is grounded
PE
Enclosure panel
Metal plate
Grounding surface
(remove any paint or sealant)
E
Cable clamp
Motor
G – Motor
H – Cable clamp
I – Ground plate (scrape off any visible paint)
J – EMC noise filter
K – Make sure the ground wire is grounded
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
YEG
Drive
Grounding surface
(remove any paint or sealant)
Motor cable (braided shield cable, max. 10 m)
Ground the cable shield