<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<21> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
<26> The setting range is 0.0 to 66.0 in AOLV/PM.
<27> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<29> The setting range varies according to the motor code entered to E5-01 when using OLV/PM. The setting range is 0.0 to 400.0 Hz when E5-01
is set to FFFFH.
<30> The setting value is F in OLV.
E2: Motor 1 Parameters
No.(Addr.)
Name
E2-01
Motor Rated Current
(30EH)
E2-02
Motor Rated Slip
(30FH)
E2-03
Motor No-Load Current
(310H)
E2-04
Number of Motor Poles
(311H)
E2-05
Motor Line-to-Line Resistance
(312H)
E2-06
Motor Leakage Inductance
(313H)
E2-07
Motor Iron-Core Saturation
(314H)
Coefficient 1
E2-08
Motor Iron-Core Saturation
(315H)
Coefficient 2
E2-09
Motor Mechanical Loss
(316H)
E2-10
Motor Iron Loss for Torque
(317H)
Compensation
E2-11
Motor Rated Power
(318H)
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<19> This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01. The value will
have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer to
and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the motor nameplate full load current in Amps. Automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the motor rated slip. Automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the no-load current for the motor. Automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the number of motor poles. Automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the phase-to-phase motor resistance. Automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage.
Automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the motor iron saturation coefficient at 50% of magnetic flux. Automatically set during
Auto-Tuning.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the motor iron saturation coefficient at 75% of magnetic flux. Automatically set during
Auto-Tuning.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the motor mechanical loss as a percentage of motor rated power (kW).
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the motor iron loss.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the motor rated power in kilowatts (1 HP = 0.746 kW). Automatically set during
Auto-Tuning.
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
B.3 Parameter Table
Setting
Page
Default:
<9>
Min: 10% of drive rated
common_
TMonly
current
Max: 200% of drive
rated current
<19>
Default:
<9>
common_
TMonly
Min: 0.00 Hz
Max: 20.00 Hz
Default:
<9>
common_
TMonly
Min: 0 A
Max: E2-01
<19>
Default: 4
common_
TMonly
Min: 2
Max: 48
Default:
<9>
common_
TMonly
Min: 0.000 Ω
Max: 65.000 Ω
common_
Default:
<9>
TMonly
Min: 0.0%
Max: 40.0%
common_
Default: 0.50
TMonly
Min: E2-07
Max: 0.50
common_
Default: 0.75
TMonly
Min: E2-07
Max: 0.75
Default: 0.0%
common_
TMonly
Min: 0.0%
Max: 10.0%
Default:
<9>
common_
TMonly
Min: 0 W
Max: 65535 W
common_
Default:
<9>
TMonly
Min: 0.00 kW
Max: 650.00 kW
Table A.2
and
Table
198
198
199
199
199
199
199
199
200
200
200
A.3)
B
415