YASKAWA A1000 Series Technical Manual page 433

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

No.(Addr.)
Name
H5-04
Stopping Method After
(428H)
Communication Error (CE)
H5-05
Communication Fault Detection
(429H)
Selection
H5-06
Drive Transmit Wait Time
(42AH)
H5-07
RTS Control Selection
(42BH)
H5-09
CE Detection Time
(435H)
H5-10
Unit Selection for MEMOBUS/
(436H)
Modbus Register 0025H
H5-11
Communications ENTER Function
(43CH)
Selection
H5-12
Run Command Method Selection
(43DH)
<32> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
H6: Pulse Train Input/Output
No.(Addr.)
Name
H6-01
Pulse Train Input Terminal RP
(42CH)
Function Selection
H6-02
(42DH)
Pulse Train Input Scaling
H6-03
(42EH)
Pulse Train Input Gain
H6-04
(42FH)
Pulse Train Input Bias
H6-05
(430H)
Pulse Train Input Filter Time
H6-06
(431H)
Pulse Train Monitor Selection
H6-07
(432H)
Pulse Train Monitor Scaling
H6-08
Pulse Train Input Minimum
(43FH)
Frequency
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
All Modes
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
All Modes
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault will occur.
All Modes
Set the wait time between receiving and sending data.
All Modes
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
All Modes
Sets the time required to detect a communications error. Adjustment may be needed when
networking several drives.
All Modes
0: 0.1 V units
1: 1 V units
All Modes
0: Drive requires an Enter command before accepting any changes to parameter settings.
1: Parameter changes are activated immediately without the Enter command (same as V7).
All Modes
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
All Modes
0: Frequency reference
1: PID feedback value
2: PID setpoint value
3: V/f Control with Simple PG feedback (possible only when using motor 1 in V/f Control)
All Modes
Sets the terminal RP input signal frequency that is equal to 100% of the value selected in H6-01.
All Modes
Sets the level of the value selected in H6-01 when a frequency with the value set in H6-02 is
input.
All Modes
Sets the level of the value selected in H6-01 when 0 Hz is input.
All Modes
Sets the pulse train input filter time constant.
All Modes
Select the pulse train monitor output function (value of the
Example: To select U5-01, set "501".
All Modes
Sets the terminal MP output signal frequency when the monitor value is 100%. To have the
pulse train monitor output equal the output frequency, set H6-06 to 2 and H6-07 to 0.
All Modes
Sets the minimum frequency for the pulse train input to be detected. Enabled when H6-01 = 0,
1, or 2.
Description
Description
-
part of U -
B.3 Parameter Table
Setting
common_
TMonly
Default: 0
Min: 0
Max: 3
common_
Default: 0
TMonly
Min: 0
Max: 1
Default: 5 ms
common_
TMonly
Min: 5 ms
Max: 65 ms
common_
Default: 1
TMonly
Min: 0
Max: 1
common_
Default: 2.0 s
TMonly
Min: 0.0 s
Max: 10.0 s
common_
Default: 0
TMonly
Min: 0
Max: 1
common_
Default: 1
TMonly
Min: 0
Max: 1
common_
Default: 0
TMonly
Min: 0
Max: 1
Setting
common_
TMonly
Default: 0
Min: 0
Max: 3
Default: 1440 Hz
common_
TMonly
Min: 1000 Hz
Max: 32000 Hz
common_
Default: 100.0%
TMonly
Min: 0.0%
Max: 1000.0%
Default: 0.0%
common_
TMonly
Min: -100.0%
Max: 100.0%
Default: 0.10 s
common_
TMonly
Min: 0.00 s
Max: 2.00 s
common_
Default: 102
TMonly
Min: 000
).
Max: 809
common_
Default: 1440 Hz
TMonly
Min: 0 Hz
Max: 32000 Hz
common_
Default: 0.5 Hz
TMonly
Min: 0.1 Hz
Max: 1000.0 Hz
Page
482
482
483
483
483
483
483
484
Page
241
242
243
243
243
243
243
243
B
433