B.4 Control Mode Dependent Parameter Default Values
B.4 Control Mode Dependent Parameter Default Values
The tables below list parameters that depend on the control mode selection (A1-02 for motor 1, E3-01 for motor 2).
These parameters are initialized to the shown values if the control mode is changed.
◆ A1-02 (Motor 1 Control Mode) Dependent Parameters
Table B.2 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values
No.
Name
b2-01
DC Injection Braking Start Frequency
b2-04
DC Injection Braking Time at Stop
b3-01
Speed Search Selection at Start
b3-02
Speed Search Deactivation Current
b3-14
Bi-Directional Speed Search Selection
b8-01
Energy Saving Control Selection
b8-02
Energy Saving Gain
b8-03
Energy Saving Control Filter Time Constant
C2-01
S-Curve Time at Acceleration Start
C3-01
Slip Compensation Gain
C3-02
Slip Compensation Primary Delay Time
C4-01
Torque Compensation Gain
C4-02
Torque Compensation Primary Delay Time
C5-01
ASR Proportional Gain 1
C5-02
ASR Integral Time 1
C5-03
ASR Proportional Gain 2
C5-04
ASR Integral Time 2
C5-06
ASR Primary Delay Time Constant
C6-02
Carrier Frequency Selection
E1-04 to
The default setting of these parameters depends on the control mode but also on the drive capacity. Refer to
E1-10
F1-05
PG 1 Rotation Selection
F1-09
Overspeed Detection Delay Time
L1-01
Motor Overload Protection Selection
L3-20
DC Bus Voltage Adjustment Gain
L3-21
Accel/Decel Rate Calculation Gain
L4-02
Speed Agreement Detection Width
L4-04
Speed Agreement Detection Width (+/–)
L8-38
Carrier Frequency Reduction Selection
L8-40
Carrier Frequency Reduction Off Delay Time
o1-03
Digital Operator Display Selection
o1-04
V/f Pattern Display Unit
<9> Default setting is determined by the drive model (o2-04) and duty selection (C6-01).
454
Setting Range
Resolution
0.0 to 10.0
0.1
0.00 to 10.00
0.01 s
0 to 1
–
0 to 200
1%
0 to 1
1
0 to 1
–
0.0 to 10.0
0.1
0.00 to 10.00
0.01 s
0.00 to 10.00
0.01 s
0.0 to 2.5
0.1
0 to 10000
1 ms
0.00 to 2.50
0.01
0 to 10000
1 ms
0.00 to 300.00
0.01
0.000 to 10.000
0.001 s
0.00 to 300.00
0.01
0.000 to 10.000
0.001 s
0.000 to 0.500
0.001 s
1 to F
–
0 to 1
–
0.0 to 2.0
0.1 s
0 to 4
–
0.00 to 5.00
0.01
0.00 to 10.00
0.01
0.0 to 20.0
0.1
0.0 to 20.0
0.1
0 to 2
1
0.00 to 2.00
0.01 s
0 to 3
1
0 to 1
1
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Control Modes (A1-02)
V/f (0)
V/f w/PG (1)
OLV (2)
0.5 Hz
0.5 Hz
0.5 Hz
0.50
0.50
0.50
0
1
0
120
–
100
1
0
1
0
0
0
–
–
0.7
0.50,
2.00
(Motor
–
–
Capacity:
55 kW and
above)
0.20
0.20
0.20
0.0
–
1.0
2000
–
200
1.00
1.00
1.00
200
200
20
–
0.20
–
–
0.200
–
–
0.02
–
–
0.050
–
–
–
–
7
7
7
<9>
<9>
<9>
V/f Pattern Default Values on page
0
0
0
–
1.0
–
1
1
1
1.00
1.00
0.30
1.00
1.00
1.00
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
<9>
<9>
<9>
0.50
0.50
0.50
0
0
0
–
–
–
CLV (3)
0.5 Hz
0.50
1
–
1
0
1.0
0.01,
0.05
(Motor
Capacity:
55 kW and
above)
0.20
1.0
–
–
–
20.00
0.500
20.00
0.500
0.004
7
<9>
456.
0
0.0
1
0.30
1.00
2.0 Hz
2.0 Hz
<9>
0.50
0
0