YASKAWA A1000 Series Technical Manual page 416

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

B.3 Parameter Table
E3: V/f Pattern for Motor 2
These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).
No.(Addr.)
Name
E3-01
Motor 2 Control Mode Selection
(319H)
E3-04
Motor 2 Maximum Output
(31AH)
Frequency
E3-05
Motor 2 Maximum Voltage
(31BH)
E3-06
Motor 2 Base Frequency
(31CH)
E3-07
Motor 2 Mid Output Frequency
(31DH)
E3-08
Motor 2 Mid Output Frequency
(31EH)
Voltage
E3-09
Motor 2 Minimum Output
(31FH)
Frequency
E3-10
Motor 2 Minimum Output
(320H)
Frequency Voltage
E3-11
Motor 2 Mid Output Frequency 2
(345H)
E3-12
Motor 2 Mid Output Frequency
(346H)
Voltage 2
<24>
E3-13
Motor 2 Base Voltage
(347H)
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<24> Parameter ignored when E3-11 (Motor 2 Mid Output Frequency 2) and E3-12 (Motor 2 Mid Output Frequency Voltage 2) are set to 0.
<25> Default setting depends on the control mode for motor 2 set in parameter E3-01. The value shown here is for V/f Control.
<26> The setting range is 0.0 to 66.0 in AOLV/PM.
<27> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
E4: Motor 2 Parameters
These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).
No.(Addr.)
Name
E4-01
Motor 2 Rated Current
(321H)
E4-02
Motor 2 Rated Slip
(322H)
E4-03
Motor 2 Rated No-Load Current
(323H)
E4-04
Motor 2 Motor Poles
(324H)
E4-05
Motor 2 Line-to-Line Resistance
(325H)
416
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
V/f
V/f w/PG
OLV/PM
AOLV/PM
These parameters are only applicable when E1-03 is set to F.
To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the
setting for E3-08 will be disregarded. Ensure that the four frequencies are set according to these
rules or an oPE10 fault will occur:
E3-09 ≤ E3-07 < E3-06 ≤ Ε3−11 ≤ E3-04
Output Voltage (V)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09
Note: E3-07 and E3-08 are only available in the following control modes: V/f, V/f w/PG and
OLV.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the full load current for motor 2. Automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the rated slip for motor 2. Automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the no-load current for motor 2. Automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the number of poles of motor 2. Automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the phase-to-phase resistance for motor 2. Automatically set during Auto-Tuning.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
E3-07 E3-06 E3-11 E3-04
Frequency (Hz)
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Setting
common_
TMonly
Default: 0
Min: 0
Max: 3
Default:
<25>
Min: 40.0
Max: 400.0
Default:
<18>
Min: 0.0 V
Max: 255.0 V
<18>
common_
TMonly
Default:
<25>
Min: 0.0
Max: E3-04
Default:
<25>
Min: 0.0
Max: E3-04
Default:
<18> <25>
Min: 0.0 V
Max: 255.0 V
<18>
Default:
<25>
Min: 0.0
Max: E3-04
Default:
<18> <25>
Min: 0.0 V
Max: 255.0 V
<18>
Default: 0.0
<24>
Min: 0.0
Max: E3-04
<26>
Default: 0.0 V
<18>
Min: 0.0 V
Max: 255.0 V
<18>
Default: 0.0 V
<18> <27>
Min: 0.0 V
Max: 255.0 V
<18>
Setting
Default:
<9>
Min: 10% of drive rated
common_
TMonly
current
Max: 200% of drive
rated current
<19>
Default:
<9>
common_
TMonly
Min: 0.00 Hz
Max: 20.00 Hz
<19>
Default:
<9>
common_
TMonly
Min: 0 A
Max: E4-01
<19>
Default: 4
common_
TMonly
Min: 2
Max: 48
Default:
<9>
common_
Min: 0.000 Ω
TMonly
Max: 65.000 Ω
Page
201
201
201
201
201
201
201
201
201
201
201
Page
202
202
202
203
203

Hide quick links:

Advertisement

Table of Contents
loading