YASKAWA A1000 Series Technical Manual page 231

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

Setting 1A: During reverse
A digital output set for "During reverse" will close whenever the drive is running the motor in the reverse direction.
Status
Open
Motor is being driven in the forward direction or stopped.
Closed
Motor is being driven in reverse.
Figure 5.75
FWD Run command
Setting 1B: During baseblock (N.C.)
Output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not
switch and no main circuit voltage is output.
Status
Open
Baseblock is being executed.
Closed
Drive is not in a baseblock state.
Setting 1C: Motor 2 selection
Indicates which motor is selected when another output terminal is set up to switch drive operation between two motors
(H1-
= 16).
Refer to Setting 16: Motor 2 selection on page 219
Status
Open
Motor 1 is selected.
Closed
Motor 2 is selected.
Setting 1D: During regeneration
Terminal closes when the motor is driven in the regenerative mode.
Setting 1E: Restart enabled
An output set for "Restart enabled" closes once the drive begins attempting to restart after a fault has occurred.
The fault restart function allows the drive to automatically clear a fault. The terminal set to 1E will close after the fault is
cleared and the drive has begun attempting to restart. If the drive cannot successfully restart within the number of
attempts permitted by L5-01, then a fault will be triggered and the terminal set to 1E will open.
Restart on page 263
for details on automatic restart.
Setting 1F: Motor overload alarm (oL1)
An output programmed for this function will close when the motor overload level estimated by the oL1 fault detection
exceeds 90% of the oL1 detection level.
Setting 20: Drive overheat pre-alarm (oH)
Output closes whenever the drive heatsink temperature reaches the level specified by parameter L8-02.
Overheat Alarm Level on page 269
Setting 22: Mechanical weakening detection
Output closes when a mechanical weakening situation is detected.
page 266
for details.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Output frequency
REV Run command
During Reverse
Figure 5.75 Reverse Direction Output Example Time Chart
Refer to L1-01: Motor Overload Protection Selection on page
for details on drive overheat detection.
Description
OFF
ON
Description
for details on switching motors.
Description
Refer to Mechanical Weakening Detection on
5.7 H: Terminal Functions
common_
TMonly
time
Refer to L5: Fault
244.
Refer to L8-02: