7.4 Cooling Fan and Circulation Fan
2.
Guide the lead wires so that they are held in place by the cable hooks and place the circulation fan connectors
between the fan and fan unit.
Figure 7.38
3.
Position the protective tube so that the fan connector sits in the center of the protective tube. (Only for circuit
Board Cooling Fan)
4.
Guide lead wires through the hooks provided so that the wires are held in place.
Figure 7.39
5.
Double check the relay connector to ensure that it is properly connected.
Installing the Cooling Fan Unit
1.
Reverse the procedure described above to reinstall the cooling fan unit.
Figure 7.40
2.
Reattach the covers and digital operator.
3.
Turn the power supply back on and reset the cooling fan operation time for the Maintenance Monitor by setting
o4-03 to 0.
368
Cooling Fan B3
Relay Connector
Figure 7.38 Cooling Fan Wiring: 4A0515 and 4A0675
Protective tube
Circuit Board Cooling Fan B6
Relay Connector
Figure 7.39 Cooling Fan Wiring: 4A0515 and 4A0675
Figure 7.40 Installing the Cooling Fan Units: 4A0515 and 4A0675
Relay Connector
Cooling Fan B2
Cooling Fan B1
Cooling Fan B5
Cooling Fan B4
Circuit Board Cooling Fan B7
Relay Connector