D.3 UL Standards

The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product
testing and evaluation, and determined that their stringent standards for product safety have been met. For a product to
receive UL certification, all components inside that product must also receive UL certification.
Figure D.6

◆ UL Standards Compliance

This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions
described below must be met to maintain compliance when using this drive in combination with other equipment:
Installation Area
Do not install the drive to an area greater than pollution severity 2 (UL standard).
Main Circuit Terminal Wiring
Cable Connectors
Yaskawa recommends using UL-listed copper wires (rated at 75°C), and closed-loop connectors or CSA-certified ring
connectors sized for the selected wire gauge to maintain proper clearances when wiring the drive. Use the correct crimp
tool to install connectors per manufacturer recommendation.
manufactured by JST Corporation.
Table D.3 Closed-Loop Crimp Terminal Size (JIS C 2805) (same for 200 V and 400 V)
Wire Gauge
mm
2
(AWG)
0.75 (18)
1.25 (16)
2 (14)
3.5/5.5 (12/10)
8 (8)
14 (6)
22 (4)
30/38 (3/2)
50/60 (1/ 1/0)
80 (2/0)
100 (4/0)
150 (250/300MCM)
200 (400MCM)
325 (600/650MCM)
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Figure D.6 UL/cUL Mark
Terminal Screws
Crimp Terminal Model Numbers
M3.5
R1.25-3.5
M4
R1.25-4
M3.5
R1.25-3.5
M4
R1.25-4
M3.5
R2-3.5
M4
R2-4
M5
R2-5
M6
R2-6
M4
R5.5-4
M5
R5.5-5
M6
R5.5-6
M8
R5.5-8
M4
8-4
M5
R8-5
M6
R8-6
M8
R8-8
M4
14-4
M5
R14-5
M6
R14-6
M8
R14-8
M10
R22-10
M12
R22-12
M12
R38-12
M12
R60-12
M12
R80-12
M12
R100-12
M10
150-10
M12
150-12
M10
200-10
M12
R200-12
M12
325-12
Table D.3
lists a suitable closed-loop connector
<1>
D.3 UL Standards
Tightening Torque
N m (lb in.)
0.8 to 1.0 (7.1 to 8.9)
1.2 to 1.5 (10.6 to 13.3)
0.8 to 1.0 (7.1 to 8.9)
1.2 to 1.5 (10.6 to 13.3)
0.8 to 1.0 (7.1 to 8.9)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
4.0 to 5.0 (35.4 to 44.3)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
4.0 to 5.0 (35.4 to 44.3)
9.0 to 11.0 (79.7 to 97.4)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
4.0 to 5.0 (35.4 to 44.3)
9.0 to 11.0 (79.7 to 97.4)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
4.0 to 5.0 (35.4 to 44.3)
9.0 to 11.0 (79.7 to 97.4)
18.0 to 23.0 (159.0 to 204.0)
32.0 to 40.0 (284.0 to 354.0)
32.0 to 40.0 (284.0 to 354.0)
32.0 to 40.0 (284.0 to 354.0)
32.0 to 40.0 (284.0 to 354.0)
32.0 to 40.0 (284.0 to 354.0)
18.0 to 23.0 (159.0 to 204.0)
32.0 to 40.0 (284.0 to 354.0)
18.0 to 23.0 (159.0 to 204.0)
32.0 to 40.0 (284.0 to 354.0)
32.0 to 40.0 (284.0 to 354.0)