o4-09: IGBT Maintenance Setting
Sets the value of the IGBT maintenance time displayed in U4-07 as a percentage of the total expected performance life.
This value should be reset to 0 when the IGBTs have been replaced.
Note: The actual maintenance time will depend on the environment where the drive is used.
No.
o4-09
o4-11: U2, U3 Initialization
When the drive is initialized, the fault trace and fault history monitors (U2-
o4-11 can be used to reset them.
No.
o4-11
Setting 0: No action
The drive keeps the record already saved concerning fault trace and fault history.
Setting 1: Reset fault data
Resets the data for the U2-
erased and the display returns to 0.
o4-12: kWh Monitor Initialization
The kWh monitors U4-10 and U4-11 are not initialized when power is shut off or the drive is initialized. Use o4-12 to
manually reset them.
No.
o4-12
Setting 0: No Action
The kWh data are kept as they are.
Setting 1: Reset kWh Data
Resets the kWh counter. The monitors U4-10 and U4-11 will display "0" after they are initialized. Once o4-12 is set to 1
and the ENTER key is pressed, kWh data is erased and the display returns to 0.
o4-13: Number of Run Commands Counter Initialization
The Run command counter displayed in U4-02 is not reset when the power is cycled or the drive is initialized. Use o4-13
to reset U4-02.
No.
o4-13
Setting 0: No Action
The Run command data are kept as they are.
Setting 1: Number of Run Commands Counter
Resets the Run command counter. The monitor U4-02 will show 0. Once o4-13 is set to 1 and the ENTER key is pressed,
the counter value is erased and the display returns to 0.

◆ q: DriveWorksEZ Parameters

These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.

◆ r: DriveWorksEZ Connection Parameters

These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Name
IGBT Maintenance Setting
Name
U2, U3 Initialization
and U3-
monitors. Once o4-11 is set to 1 and the ENTER key is pressed, fault data is
Name
kWh Monitor Initialization
Name
Number of Run Commands Counter Initialization
5.10 o: Operator Related Settings
Setting Range
0 to 150%
and U3-
) are not reset. Parameter
Setting Range
0 or 1
Setting Range
0 or 1
Setting Range
0 or 1
Default
0%
Default
0
Default
0
Default
0
5
289