YASKAWA A1000 Series Technical Manual page 286

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

5.10 o: Operator Related Settings
o2-02: STOP Key Function Selection
Determines if the STOP key on the digital operator can still be used to stop drive operation when the drive is being
controlled from a remote source (i.e., not from digital operator).
No.
o2-02
Setting 0: Disabled
Setting 1: Enabled
The STOP key can be used to terminate drive operation, even if the Run command source is not assigned to the digital
operator. If the drive is stopped by pressing the STOP key, the Run command must be cycled to restart the drive.
o2-03: User Parameter Default Value
Once drive parameters are set up completely, the values set can be saved as user-set default values using parameter o2-
03. Once this has been done, the "Initialize Parameters" parameter (A1-03) will offer the choice of "1110: User
Initialize". Choosing A1-03 = "1110: User Initialize" will reset all parameters to the values saved as user-set defaults.
Refer to A1-03: Initialize Parameters on page 131
No.
o2-03
Setting 0: No change (awaiting command)
Setting 1: Set User Initialize values
The current parameter settings are saved as user-set default for a later User Initialize. Once o2-03 is set to 1 and the
ENTER key is pressed, the values are saved and the display returns to 0.
Setting 2: Clear User Initialize Values
All user-set defaults for "User Initialize" are cleared. Once o2-03 is set to 2 and the ENTER key is pressed, the values are
erased and the display returns to 0.
o2-04: Drive Model Selection
This parameter must be set when replacing the control board or the terminal board for any reason. For information on the
drive model selection, see
NOTICE: Drive performance will suffer if the correct drive capacity is not set to o2-04, and protective functions will fail to operate
properly.
No.
o2-04
o2-05: Frequency Reference Setting Method Selection
Determines if the ENTER key must be pressed after changing the frequency reference using the digital operator while in
the Drive Mode.
No.
o2-05
Setting 0: ENTER key required
Every time the frequency reference is changed using the digital operator, the ENTER key must be pressed for the drive to
accept the change.
Setting 1: ENTER key not required
The output frequency changes immediately when the reference is changed by the up or down arrow keys on the digital
operator. The ENTER key does not need to be pressed. The frequency reference is saved for 5 s after it is changed.
286
Name
STOP Key Function Selection
Name
User Parameter Default Value
Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01) on page
Name
Drive Model Selection
Name
Frequency Reference Setting Method Selection
for details on drive initialization.
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
Setting Range
0 or 1
Setting Range
0 to 2
457.
Setting Range
Determined by drive
-
Setting Range
0 or 1
Default
1
Default
0
Default
capacity
Default
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents