D2: Frequency Upper/Lower Limits - Omron JZA User Manual

Compact general purpose inverter 200 v class three-phase input 0.1 to 0.4 kw 200 v class single-phase input 0.1 to 1.5 kw 400 v class three-phase input 0.2 to 4.0 kw
Hide thumbs Also See for JZA:
Table of Contents

Advertisement

Reference
Frequency Reference 8 (d1-08)
Jog Frequency Reference (d1-17)
<1> The Jog frequency overrides the frequency reference being used.
Frequency
reference
FWD (REV) Run/Stop
Multi-step Speed Ref. 1
Multi-step Speed Ref. 2
Multi-step Speed Ref. 3
Jog Reference
u

d2: Frequency Upper/Lower Limits

By entering upper or lower frequency limits, the drive programmer can prevent operation of the drive above or below
levels that may cause resonance and or equipment damage.
n
d2-01: Frequency Reference Upper Limit
Sets the maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.
No.
d2-01
n
d2-02: Frequency Reference Lower Limit
Sets the minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
If a lower reference than this value is input, the drive will run at the d2-02 level. If the drive is started with a lower reference
than d2-02, it will accelerate up to d2-02.
No.
d2-02
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Multi-Step
Speed
H1- = 3
ON
<1>
d1-04
d1-03
d1-02
d1-01
(A1)
ON
ON
ON
Figure 5.9 Preset Reference Timing Diagram
Parameter Name
Frequency Reference Upper Limit
Parameter Name
Frequency Reference Lower Limit
Internal frequency
reference
d2-01
Operating
range
d2-02
Figure 5.10 Frequency Reference: Upper and Lower Limits
Multi-Step
Multi-Step
Speed 2
H1- = 4
H1- = 5
ON
d1-08
d1-07
d1-06
d1-05
ON
ON
ON
ON
ON
Setting Range
0.0 to 110.0%
Setting Range
0.0 to 110.0%
Frequency Reference Upper Limit
Frequency Reference Lower Limit
Set frequency reference
5.4 d: Reference Settings
Jog Reference
Speed 3
H1- = 6
ON
OFF
ON
d1-17
Time
ON
ON
Default
100.0%
Default
0.0%
5
83