2
Installing Hardware for the G700 Media Gateway and S8300 Media Server
Installation and Cabling
Fault Conditions
If the AC outlet tests that follow reveal any of the following conditions, they must be corrected BEFORE
the system is to be installed.
Verify Ground Using an Ideal 61-035 Circuit Tester (or equivalent)
1
Plug the circuit tester into the outlet that you want to test.
If the circuit is properly grounded, the yellow and white lights on the tester illuminate.
2
Unplug the tester.
Verify Voltages Using a Volt-Ohm Millimeter (VOM) (U.S. and countries using 110 to 125
Vac power)
1
Ensure that the VOM is set to read Volts AC
NOTE:
The following example is for North American voltages (110 to 125 Vac). Use the
appropriate voltages for local power.
2
Set the VOM to the lowest scale on which you can read 130 Vac.
96
Open ground
Hot and neutral reversed
Open hot
Open neutral
Hot and ground reversed
!
WARNING:
Hazardous voltages are present during this test. Follow all instructions carefully
when working the AC power line voltages.
!
WARNING:
If the tester indicates any type of ground fault, your customer must contact a licensed
electrician. DO NOT install the system.
!
WARNING:
Hazardous voltages are present during this test. Follow all instructions carefully
when working with AC power line voltages.