Functions

4.2.3.2 TIP Mode

TIP mode is a time-limited variant of JOG mode. The time limit can be set via a parame-
ter.
No.
1
2
3
4
16
Product manual | Version: 1.1.0
Proportional Valve Module 2-3-4
Event
Set SPL_EN to "0" and set
PH_TIP_MODE parameter to
"1"
Set JOG_POS to "1"
Set JOG_NEG to "1"
Set JOG_POS to "1"
SetJOG_NEG to "1"
Figure 8: Actual Value Curve in TIP Mode
Description/Behavior
TIP mode is activated. Present actual value is held.
The present current is increased for the time T parameterized in
PH_TIP_TIME.
The present current is reduced for the time T parameterized in
PH_TIP_TIME.
A positive edge of the JOG_POS bit or the JOG_NEG bit is ig-
nored if it occurs within the PH_TIP_TIME period after the first de-
tected edge. The previous TIP action must be completely finished
for an edge change to lead to a response.
750-1632/000-100