750-1632/000-100

4.2.3 JOG/TIP Mode

In JOG/TIP mode, the valves are set manually. The actual value can only move within the
valid setpoint limits.
With corresponding parameterization, JOG/TIP mode can also be controlled via digital in-
puts DI1 and DI2. A logical "OR" operator is applied to the digital inputs and the corre-
sponding bits in the control byte.

4.2.3.1 JOG Mode

In JOG mode, the I/O module changes the actual value as long as the signal for increas-
ing or decreasing the actual value is present, such as for an actuator moving at a fixed
speed in the specified direction until the corresponding button is released.
The function is controlled via the JOG bits (JOG_POS, JOG_NEG) or, with corresponding
parameterization, via digital inputs DI 1 and DI 2.
No.
1
2
3
4
Product manual | Version: 1.1.0
Proportional Valve Module 2-3-4
Event
Set SPL_EN to "0"
Set JOG_POS to "1"
Set JOG_POS to "0"
Set JOG_NEG to "1"
Set JOG_NEG to "0"
Set JOG_POS to "1"
Set JOG_NEG to "1"
Figure 7: Actual Value Curve in JOG Mode
Description/Behavior
JOG mode is activated.
Present current is held.
Present current is increased.
Present current is held.
Present current is reduced.
Present current is held.
Present current is held if both JOG bits are addressed.
Functions
15