Functions
4.2.8.2 End Stop Behavior in JOG/TIP Mode
4.2.8.2.1 Approaching the End Stop Value
No.
1
2
3
4
5
6
7
8
24
Product manual | Version: 1.1.0
Proportional Valve Module 2-3-4
Figure 14: End Stop Behavior in JOG Mode When Approaching the End Stop Value
Event
Set SPL_EN to "0"
Set JOG_POS to "1"
SetJOG_POS to "0"
Set DI to "1."
Set JOG_NEG to "1"
SetJOG_NEG to "0"
Set JOG_POS to "1"
Set DI to "1."
Set JOG_POS to "1"
Set JOG_POS to "0"
Description/Behavior
JOG mode is activated.
Present current is held.
Present current is increased.
The present current is then held until a new JOG_POS signal is
received.
Rising ramp stops. The actual value falls until the end stop value
is reached.
The actual value is then held.
The present current is reduced.
The actual value is then held.
Present current is increased.
Rising ramp stops.
The actual value drops until the end stop value is reached.
The actual value is then held.
Present current is increased (even if the DI is still active).
Present current is held.
750-1632/000-100