Figure 9 Setpoint Specification In Emergency Operation - WAGO 750 Product Manual

Table of Contents

Advertisement

Functions
No.
1
2
3
4
5
6
7
8
Note
Ensure the power supply via power jumper contacts and data contacts
Emergency operation can only be ensured if the power supply is applied via the power
jumper contacts and data contacts. If one of the two power supplies is interrupted, the I/O
module cannot switch to emergency operation.
To ensure a permanent power supply, the 750-613 I/O module can be used as the supply
module, for example.
18
Product manual | Version: 1.1.0
Proportional Valve Module 2-3-4
Event
Set SPL_EN to "1."
Increase setpoint.
Local bus error occurs.
Set DI to "1" with the
DI_JOG_POS function.
Local bus error is eliminated.
Set DI to "1" with the
DI_JOG_NEG function.
Increase setpoint.
Change SPL_EN setting from
"0" to "1."
Figure 9: Setpoint Specification in Emergency Operation
Description/Behavior
Normal operation is activated.
Parameterized setpoint is approached.
Substitute value is hard-set (for PWR_EN_UseStopRamp = 0).
Substitute value is approached with stop ramp (for
PWR_EN_UseStopRamp = 1).
Actual value is increased.
Present actual value is held.
Jogging still possible.
Actual value is reduced.
The actual value is held because the substitute value strategy has
not yet been acknowledged.
Substitute value strategy is acknowledged.
Parameterized setpoint is approached.
750-1632/000-100