Table 12 Parameter Table 60 (Valve Adjustment, Valve 1) - WAGO 750 Product Manual

Table of Contents

Advertisement

Functions
Parameter Tables 160 and 161 (Valve Adjustment, Valve 1, Valve 2)
Tables 160 and 161 have identical structures. As an example, Table 160 is explained
here for valve 1.
Register Name, Type
0
1
2
3
4
40
Product manual | Version: 1.1.0
Proportional Valve Module 2-3-4
Bits, Explana-
tion
VA_ENABLE,
0 ... 15
UINT
VA_MIN_A,
0 ... 15
UINT
VA_MAX_A,
0 ... 15
UINT
VA_MIN_B,
0 ... 15
UINT
VA_MAX_B,
0 ... 15
UINT
Table 12: Parameter Table 60 (Valve Adjustment, Valve 1)
Value/Range
Description
(Default)
0
Function is not executed (bypass).
1
Function is executed.
(Default)
0 ... 9000
n × 0.01 %
(Default: 0)
Compensation for valve 1 dead zone, positive
range
1000 ... 10000
n × 0.01 %
(Default:
Maximum output signal, valve 1, positive range
10000)
0 ... 9000
n × 0.01 %
(Default: 0)
Compensation for valve 1 dead zone, negative
range
1000 ... 10000
n × 0.01 %
(Default:
Maximum output signal, valve 1, negative range
10000)
750-1632/000-100

Advertisement

Table of Contents
loading

This manual is also suitable for:

753

Table of Contents