4.2.9.2 Approaching the Substitute Value

The substitute value can be approached in two ways:
• "Hard" approach to substitute value: There is no ramp; instead, the parameterized sub-
stitute value is output directly.
• "Soft" approach to substitute value: The stop ramp is used to approach the substitute
value.
When the fault on the local bus is cleared, the value continues to be held until this state
has been acknowledged; see
knowledgement
The parameters for configuration are described in
Module Parameters) [} 33]
Handling, Valve 1, Valve 2)
No.
1
2
3
4
5
6
7
8
9
28
Product manual | Version: 1.1.0
Proportional Valve Module 2-3-4
8 Exiting the Substitute Value Strategy through Ac-
[} 29].
and
8 Parameter Tables 150 and 151 (Process Data
[} 34].
Figure 17: Substitute Value Strategy When Approaching the Substitute Value
Event
Set SPL_EN to "1"
Increase setpoint.
Local bus error occurs.
Local bus error is eliminated.
Positive edge of SPL_EN
Set PWR_EN_UseStoppRamp
to "1"
Local bus error occurs.
Local bus error is eliminated.
Change SPL_EN setting from
"0" to "1"
8 Parameter Table 140 (Additional
Description/Behavior
Normal operation is activated.
Parameterized setpoint is approached.
Parameterized substitute value is hard-set.
Parameterized substitute value is held.
Substitute value strategy is acknowledged.
Parameterized setpoint is approached.
The stop ramp is configured for approaching the substitute value.
The substitute value according to the parameterization is ap-
proached via the stop ramp.
Parameterized substitute value is held.
Parameterized setpoint is approached.
750-1632/000-100