Diagnostics
7 Diagnostics
7.1 Diagnostics via Process Image
Bit
KBUS_STA-
TUS.ERR
_MOD
KBUS_STA-
TUS.ERR
_CHx
Vx_STA-
TUS.READY
Vx_STA-
TUS.ON
_TARGET
68
Product manual | Version: 1.1.0
Proportional Valve Module 2-3-4
State
Explanation
Cause
0
No
–
module error
1
Module error
Undervoltage
Overtemperature
0
No
–
channel error
1
Channel error,
Short circuit, over-
channel x
load
Wire break
0
Output stage
Undervoltage
deactivated
Short circuit, over-
load
Wire break
Overtemperature
Error during teach-in
function
End stop behavior
Output stage was
switched off via con-
troller
1
Output stage
–
activated
0
The actual
The current is not yet
value deviates
reached after a set-
from the set-
point change.
point
1
Setpoint
–
reached
750-1632/000-100
Table 37: Diagnostics via Process Image
Remedy
–
Check supply voltage.
Reduce ambient temperature or target cur-
rent.
–
Check wiring.
Check wiring.
Check supply voltage.
Check wiring.
Check wiring.
Reduce ambient temperature or target cur-
rent.
Cancel teach-in function (TEACH_EN bit =
0)
Clear limit stop switch.
Switch output stage on.
–
Evaluate depending on the application
(e.g., increase on-target window, set nomi-
nal current to the value specified by the
manufacturer).
–