9.7

DESIGN CONSIDERATIONS

This section describes design and programming considerations for using the waveform generator.
9.7.1

Dead Time and Duty Cycle

Short dead times have little effect on the duty cycle if the pulse is relatively wide; however, longer
dead times with narrower pulses can affect the duty cycle (Figure 9-14). No minimum pulse width
is imposed by the hardware, so it is possible to deassert an output for the entire period if the total
dead time is greater than the pulse width. For this reason, software should ensure that the pulse
width is at least 3 × T
DEAD
WG_COUNT
1
WG_COUNT=
WG_COMP
Dead Time
(DT)
WFG
P6.0 / WG1#
=DT x WFG#
P6.1 / WG1
=DT x WFG
= Power Output Driver Enabled
9-20
.
Dead Time
Increased
Mode 0, OP0 = OP1 = 1, PH1.0 = PH1.1 = PH1.2 = 1
Figure 9-14. Effect of Dead Time on Duty Cycle
Get other manuals https://www.bkmanuals.com
Dead Time
Increased
No WFG1 Output
= Dead Time
A2660-01