Remote data Tags and Timeouts
Data Tag
Timeout
Format
Mantracourt Electronics Limited
Enter the Data Tag (in hexadecimal) to supply data to this input.
You can click the 'P' button to retrieve the Data Tag of a module by pairing to it
which is usually initiated by power cycling the module.
Clicking the X button zeroes the entered Data Tag.
Enter the timeout in milliseconds for this input. If a new Data Provider packet
does not arrive within this time and reference to this input value (via token
<V1> for example) will result in an output of -------. This also applies to a gross
or net reading derived from this input.
Describe the format that this value is to take when output. You specify integer
digits and decimal places by entering a format consisting of zeroes and decimal
points. i.e. 00.000
The integer value of data takes precedent over your defined
format so if you defined a format of 0.0 and data of value
100.8265 arrived it would be represented as 100.8
Examples
Format
0.0
0.0
00.000
00.000
0000.00
Resolution
It is possible to set the resolution (the smallest unit of change) of the output
results by including the numeric value in the format. i.e.
00.005 would only represent the value in steps of 00.005
Value
1.2
100.8
6.1234
123.4567
12.0
275
Representation
1.2
100.8
06.123
123.456
0012.00
T24 Telemetry User Manual