Configuration Examples
LED Display from a Single Source
We want to put data from a T24-SA onto a large LED display.
We will use the out of the box rate of 3 per second. The display only needs the ASCII data followed by a carriage
return.
Assuming the T24-SA sends its data on Data Tag C675
Line1=<V1><0D>
V1Format=00.000
Timeout1=2000
ValueDataTag1=C675
PrintDataTag=C675
MinInterval=100
LineDelay=0
PrintOnError=1
SwitchMode=1
Summed LED Display from Dual Source
We want to put the summed Net data from a pair of T24-SAs onto a large LED display. We want the switch input
of the T24-SO to toggle between Gross and zeroed net mode. (The printed output will reflect whether the module
is in gross or zeroed net mode).
We will use the out of the box rate of 3 per second. The display only needs the ASCII data followed by a carriage
return.
Assuming the T24-SAs send data on Data Tag C675 and FF34
Parameter settings:
Line1=<NET><0D>
FormatSUM=00.000
ValueDataTag1=C675
ValueDataTag2=FF34
PrintTrigger=C675
MinInterval=100
LineDelay=0
PrintOnError=1
SwitchMode=1