Safety
Correct use in accordance with these instructions
2.2 Correct use in
accordance with
these instructions
The device is designed and con-
structed exclusively for the intended
use described herein.
Correct use in non-hazard areas
The flow monitor serves exclusively
to monitor the continuous flow of liq-
uids within a temperature range of
-20 °C to 120 °C (optional: 160 °C) at
a maximum operating pressure of:
250 bar (brass version) and 300 bar
(stainless steel version).
Correct use in explosion-hazard
zones
For employment in explosion-hazard
zones, changed conditions apply for
the intended use.
The intended use in explosion-hazard
zones is described in the Operating
Instructions for "SW-08 (1") Module
ATEX" .
Intended use in explosion-hazard
zones includes the observance of all
specifications in these Operating
Instructions, as well as those for
"SW-08 (1") Module ATEX ".
Any additional or different application,
above and beyond the correct use in
accordance with these instructions, is
deemed as incorrect use.
10
WARNING!
Danger due to incorrect use!
Incorrect use of the flow monitor
may result in dangerous situations.
–
Use the flow monitor only
within the stipulated perform-
ance limits
–
Do not subject the flow mon-
itor to severe temperature fluc-
tuations
–
Do not use the flow monitor
with quick acting valves
–
Do not use the flow monitor
with solenoid valves
–
Do not subject the flow mon-
itor to vibrations
–
Do not subject the flow mon-
itor to pressure surges
–
Do not use the flow monitor
with media containing solids or
abrasives
–
Only use the flow monitor with
media previously approved by
the manufacturer
–
Do not use the flow monitor as
the sole monitoring device to
prevent dangerous conditions
–
Do not install the flow monitor
as a load bearing part within a
pipeline system
–
The flow monitor must be
installed so that it is protected
from damage by mechanical
force. If necessary, install an
appropriate impact protection
device.