Case 580SR Service Manual page 798

Hide thumbs Also See for 580SR:
Table of Contents

Advertisement

www.maskinisten.net
38
PERFORMANCE TEST EXAMPLE 7
7
6
5
1. High side high
2. High side hand valve closed
3. High side hose connected to high side service
connector
4. Not used
PROBLEM
Little or no cooling.
CAUSE
Improper operation of thermostatic expansion valve
(stuck open).
CONDITIONS*
Low side pressure too high. Gauge should read 1-2
bar.
High side pressure too high. Gauge should read
13.3-14.8 bar.
Evaporator air warm.
Evaporator and suction hose (to compressor) sur-
faces show considerable moisture.
CORRECTIVE PROCEDURES
1. Check for sticking expansion valve as follows:
Operate the system at maximum cooling.
Check the low side gauge. The pressure should
lower slowly.
SECTION 50 - CAB HEATING AND AIR CONDITIONING
Performance Test Example 7
4
5. Low side hose connected to low side service
connector
6. Low side hand valve closed
7. Low side hide
2. If the test indicates that the expansion valve is
defective, proceed as follows:
Discharge and recover the refrigerant from the
system.
Replace the expansion valve.
Evacuate the system.
Charge the system.
Performance test the system.
DIAGNOSIS
Thermostatic expansion valve is allowing too much
refrigerant to flow through the evaporator coils.
Valve may be stuck open.
NOTE: * test procedure based upon ambient tem-
perature of 35 °C.
For proper high side gauge reading for other ambi-
ent temperatures, refer to the pressure temperature
chart.
Copyright ©
1
2
3
F28704

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

580sr+590sr695sr

Table of Contents