Parameter Group 22-** Appl. Functions - Danfoss VLT Flow Drive FC 111 Programming Manual

Hide thumbs Also See for VLT Flow Drive FC 111:
Table of Contents

Advertisement

VLT® Flow Drive FC 111
Programming Guide
Table 376: Range:
Min: 0%
4.15.6 20-9* PI Controller
Parameters for configuring the Process PI controller.
20-91 PI Anti Windup
Default value: [1] On
Conversion index: -
Table 377: Option:
[0]
Off
Continue regulation of an error even when the output frequency cannot be increased or decreased.
[1]
On
Cease regulation of an error when the output frequency can no longer be adjusted.
20-93 PI Proportional Gain
Default value: 0.50
Conversion index: -2
Enter the process controller proportional gain. Quick control is obtained at high amplification. However, if amplification is too high,
the process may become unstable.
Table 378: Range:
Min: 0
20-94 PI Integral Time
Default value: 20 s
Conversion index: -2
Enter the process controller integral time. Obtain quick control through a short integral time, though if the integral time is too short,
the process becomes unstable. An excessively long integral time disables the integral action.
Table 379: Range:
Min: 0.10 s
20-97 PI Feed Forward Factor
Default value: 0%
Conversion index: 0
Enter the PI feed forward factor. The FF factor sends a constant fraction of the reference signal to bypass PI control. Therefore, the PI
can affect only the remaining fraction of the control signal. The FF factor can increase dynamic performance.
Table 380: Range:
Min: 0%

4.16 Parameter Group 22-** Appl. Functions

Parameter group for application monitoring functions.
4.16.1 22-0* Miscellaneous
Parameter group for extra settings.
164 | Danfoss A/S © 2021.07
Max: 200%
Parameter type: Option
Data type: u_int8
Parameter type: Range
Data type: u_int16
Max: 10
Parameter type: Range
Data type: u_int32
Max: 9999 s
Parameter type: Range
Data type: u_int16
Max: 400%
Default value: 5%
2-setup: All setups
Change during operation: True
2-setup: All setups
Change during operation: True
Default value: 0.50
2-setup: All setups
Change during operation: True
Default value: 20 s
2-setup: All setups
Change during operation: True
Default value: 0%
Parameters
AU363928304090en-000101 / 130R0982