Danfoss VLT Flow Drive FC 111 Programming Manual page 39

Hide thumbs Also See for VLT Flow Drive FC 111:
Table of Contents

Advertisement

VLT® Flow Drive FC 111
Programming Guide
0-44 [Off/Reset] Key on LCP
Default value: [1] Enabled
Conversion index: -
Table 31: Option:
[0]
Disabled
[1]
Enabled
[7]
Enable Reset Only
4.2.5 0-5* Copy/Save
Copy parameter settings between setups and to/from the LCP.
0-50 LCP Copy
Default value: [0] No copy
Conversion index: -
Table 32: Option:
[0]
No copy
No action.
[1]
All to LCP
Copy all parameters in all setups from the drive memory to the LCP memory. For service purposes,
copy all parameters to the LCP after commissioning.
[2]
All from LCP
Copy all parameters in all setups from the LCP memory to the drive memory.
[3]
Size indep. from
Copy only the parameters that are independent of the motor size. The latter selection can be used to
LCP
program several drives with the same function without disturbing motor data that is already set.
[10]
Delete LCP copy
Delete copied parameters in LCP. This function requires that LCP version is greater than or equal to
data
V11.00.
0-51 Set-up Copy
Default value: [0] No copy
Conversion index: -
Table 33: Option:
[0]
No copy
[1]
Copy from setup 1
[2]
Copy from setup 2
[9]
Copy from factory setup
4.2.6 0-6* Password
This parameter group defines password to access menus.
0-60 Main Menu Password
Default value: 0
Conversion index: -
Define the password for access to the Main Menu via the [Main Menu] key. Setting the value to 0 disables the password function.
This parameter hides after a password is defined.
Danfoss A/S © 2021.07
Parameter type: Option
Data type: u_int8
Disable the [Off/Reset] key.
Enable both off and reset functions.
Enable the reset function, and disable the off function to avoid unintended stop of the drive.
Parameter type: Option
Data type: u_int8
Parameter type: Option
Data type: u_int8
No action.
Copy from setup 1 to setup 2.
Copy from setup 2 to setup 1.
Copy factory setting to programming setup (selected in parameter 0-11 Programming Set-up).
Parameter type: Range
Data type: u_int16
2-setup: All setups
Change during operation: True
2-setup: 1 setup
Change during operation: False
2-setup: 1 setup
Change during operation: False
2-setup: 1 setup
Change during operation: True
AU363928304090en-000101 / 130R0982 | 39
Parameters