VLT® Flow Drive FC 111
Programming Guide
Table 258: Option:
[0]
[1]
[2]
14-55 Output Filter
Default value: [0] No filter
Conversion index: -
Select the type of connected output filter.
Table 259: Option:
[0]
No filter
[1]
Sine-wave filter
[3]
Sine-wave filter with feedback
[4]
dv/dt
4.11.7 14-6* Auto Derate
Parameter group for configuring automatic derating based on the output frequency of the drive.
14-61 Function at Inverter Overload
Default value: [0] Trip
Conversion index: -
When the drive issues an inverter overload warning, select whether to continue and probably trip the drive or derate the output
current.
Table 260: Option:
[0]
[1]
14-63 Min Switch Frequency
Default value: [2] 2.0 kHz
Conversion index: -
Set the lowest switch frequency allowed by the application.
Table 261: Option:
[2]
[3]
[4]
[5]
[6]
[7]
Danfoss A/S © 2021.07
Disabled
Warning
Trip
Parameter type: Option
Data type: u_int8
No filter is selected.
For backwards compatibility only.
Sine wave filter with feedback is selected.
This option is only valid for drives of the following enclosure sizes:
•
IP20, 3x380–480 V, enclosure sizes H6–H8.
Parameter type: Option
Data type: u_int8
Trip
Derate
Parameter type: Option
Data type: u_int8
2.0 kHz
3.0 kHz
4.0 kHz
5.0 kHz
6.0 kHz
8.0 kHz
2-setup: 1 setup
Change during operation: False
2-setup: All setups
Change during operation: True
2-setup: 1 setup
Change during operation: False
AU363928304090en-000101 / 130R0982 | 137
Parameters