VLT® Flow Drive FC 111
Programming Guide
0-16 Application Selection
Default value: [0] None
Conversion index: -
Select an application function from the options. When an application is selected, a set of its related parameters are set automatical-
ly.
Before selecting an option in parameter 0-16 Application Selection, set [2] Initialisation for parameter 14-22 Operation Mode to en-
sure that all parameter values are reset to default settings.
Table 21: Option:
[0]
None
[12]
Open Loop Control
[13]
Process Closed Loop Control
[14]
Constant Pressure Water Supply
[15]
Multi Pump Control Application
4.2.3 0-3* LCP Custom Readout
Parameters for configuring the custom readout value and defining custom display texts. It is possible to customize the display ele-
ments for various purposes.
Custom readout
The calculated value to be shown is based on settings in parameter 0-30 Custom Readout Unit, parameter 0-31 Custom Readout Min
Value (linear only), parameter 0-32 Custom Readout Max Value, parameter 4-14 Motor Speed High Limit [Hz], and actual speed.
Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
Min value
Liniar
units only
P 0-31
0
Illustration 6: Custom Readout
The relation depends on the type of unit selected in parameter 0-30 Custom Readout Unit:
Table 22: Speed Relation
Unit type
Dimensionless
Speed
Flow, volume
Danfoss A/S © 2021.07
Parameter type: Option
Data type: u_int8
N O T I C E
Motor Speed
Motor Speed
High limit
P 4-14 (Hz)
Speed relation
Linear
2-setup: 1 setup
Change during operation: False
AU363928304090en-000101 / 130R0982 | 35
Parameters