Table 183: Option:
[0]
Digital and ctrl.word
[1]
Digital only
[2]
Controlword only
8-02 Control Source
Default value: [1] None
Conversion index: -
Select the source of the control word.
Table 184: Option:
[0]
[1]
8-03 Control Timeout Time
Default value: Configuration dependent
Conversion index: -1
Enter the maximum time expected to pass between the reception of 2 consecutive telegrams. If this time is exceeded, it indicates
that the serial communication has stopped. The function selected in parameter 8-04 Control Timeout Function is carried out.
Table 185: Range:
Min: 0.1 s
Max: 6500 s
8-04 Control Timeout Function
Default value: [0] Off
Conversion index: -
Select the timeout function. The timeout function is activated when the control word fails to be updated within the time period
specified in parameter 8-03 Control Timeout Time.
Table 186: Option:
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[20]
[26]
104 | Danfoss A/S © 2021.07
Control by using both digital input and control word.
Control by using digital inputs only.
Control by using control word only.
Parameter type: Option
Data type: u_int8
None
FC Port
Parameter type: Range
Data type: u_int16
Default value: Configuration dependent
Parameter type: Option
Data type: u_int8
Off
Freeze output
Stop
Jogging
Max. speed
Stop and trip
Qstop and trip
N2 override release
Trip
2-setup: All setups
Change during operation: True
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: True
AU363928304090en-000101 / 130R0982
Parameters