25-51 Alternation Event
Default value: [0] External
Conversion index: -
Choose the event that will change the lead pump.
Table 454: Option:
[0]
External
[1]
Alternation time interval
[2]
Sleep mode
25-52 Alternation Time Interval
Default value: 24 h
Conversion index: -
Set the time period between automatic alternation of the lead pump.
Table 455: Range:
Min: 1 h
25-53 Alternation Timer Value
Default value: 0
Conversion index: 0
View the actual value of the alternation time interval timer.
Table 456: Range:
Min: 0
25-55 Alternate if Load <= 50%
Default value: [1] Enabled
Conversion index: -
Choose enable to change the variable-speed pump only if the pump load is less than 50%.
Table 457: Option:
[0]
[1]
Danfoss A/S © 2021.07
Parameter type: Option
Data type: u_int8
Parameter type: Range
Data type: u_int16
Max: 999 h
Parameter type: Range
Data type: VisibleString
Max: 7
Parameter type: Option
Data type: u_int8
Disabled
Enabled
2-setup: All setups
Change during operation: True
2-setup: All setups
Change during operation: True
Default value: 24 h
2-setup: All setups
Change during operation: True
Default value: 0
2-setup: All setups
Change during operation: True
AU363928304090en-000101 / 130R0982 | 187