VLT® Flow Drive FC 111
Programming Guide
[62]
Reset Counter
Input for reset of counter A.
A
[63]
Counter B (up)
Input for increment counting in the SLC counter.
[64]
Counter B
Input for decrement counting in the SLC counter.
(down)
[65]
Reset Counter B
Input for reset of counter B.
[101]
Sleep
A signal applied puts the drive into sleep mode.
[120]
Lead Pump
A signal applied puts the lead pump into start mode.
Start
[121]
Lead Pump Al-
A signal applied puts the lead pump into alternation mode.
ternation
[130]
Pump 1 Inter-
A signal applied puts the pump 1 into interlock mode.
lock
[131]
Pump 2 Inter-
A signal applied puts the pump 2 into interlock mode.
lock
[132]
Pump 3 Inter-
A signal applied puts the pump 3 into interlock mode.
lock
[133]
Pump 4 Inter-
A signal applied puts the pump 4 into interlock mode.
lock
[134]
Pump 5 Inter-
A signal applied puts the pump 5 into interlock mode.
lock
[190]
Fire Mode Ref
Enable a selection of 1 of the 8 fire mode references according to
Bit 0
[191]
Fire Mode Ref
Enable a selection of 1 of the 8 fire mode references according to
Bit 1
[192]
Fire Mode Ref
Enable a selection of 1 of the 8 fire mode references according to
Bit 2
5-11 Terminal 19 Digital Input
Default value: [0] No operation
Conversion index: -
Parameter for configuring the input function on input terminal 19.
Table 135: Option:
[0]
No operation
No reaction to signals transmitted to the terminal.
[1]
Reset
Reset the after a trip/alarm. Trip lock alarms can be reset.
[2]
Coast inverse
Leave the motor in free mode. Logic 0⇒coast stop.
[3]
Coast and reset
Reset and coast stop inverted input (NC). Leaves the motor in free mode and resets the . Logic
inverse
0⇒coast stop and reset.
[4]
Quick stop in-
Inverted input (NC). Generates a stop in accordance with the quick-stop ramp time set in parameter
verse
3-81 Quick Stop Ramp Time. After ramping down, the shaft is in free mode.
72 | Danfoss A/S © 2021.07
Parameter type: Option
Data type: u_int8
Table
133.
Table
133.
Table
133.
2-setup: All setups
Change during operation: True
AU363928304090en-000101 / 130R0982
Parameters