VLT® Flow Drive FC 111
Programming Guide
5-35 Off Delay, Digital Output
Default value: 0.01 s
Conversion index: -2
Enter the delay time before the digital output is switched off. The digital output (terminal 42/45) condition must not be interrupted
during the delay time.
Table 141: Range:
Min: 0 s
4.7.4 5-4* Relays
Parameters for configuring the timing and the output functions for the relays.
5-40 Function Relay
Default value: [0] No operation
Conversion index: -
Select options to define the function of the relays.
Table 142: Option:
[0]
No operation
[1]
Control Ready
[2]
Drive ready
[3]
Drive ready/remote
control
[4]
Standby/no warning
[5]
Drive running
[6]
Running/no warning
[7]
Run in range/no
warning
[8]
Run on ref/no warn-
ing
[9]
Alarm
[10]
Alarm or warning
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[16]
Below speed, low
[17]
Above speed, high
[19]
Below feedback, low
[20]
Above feedback, high
86 | Danfoss A/S © 2021.07
Parameter type: Range
Data type: u_int16
Max: 600 s
Parameter type: Option
Data type: u_int8
No operation.
The control board receives supply voltage.
The drive is ready for operation and applies a supply signal on the control board.
The drive is ready for operation in auto-on mode.
The drive is ready for operation. No start or stop command is given. No warnings are present.
The motor runs.
The motor runs, and no warnings are present.
The motor runs within the programmed current ranges, see parameter 4-50 Warning Current Low
and parameter 4-51 Warning Current High. No warnings are present.
The motor runs at reference speed and with no warnings.
An alarm activates output.
An alarm or warning activates output.
The motor current is outside the ranges set in parameter 4-50 Warning Current Low and parame-
ter 4-51 Warning Current High.
The motor current is lower than the limit set in parameter 4-50 Warning Current Low.
The motor current is higher than the limit set in parameter 4-51 Warning Current High.
The drive output speed is lower than the limit set in parameter 4-40 Warning Freq. Low.
The drive output speed is higher than the limit set in parameter 4-41 Warning Freq. High.
The feedback is lower than the limit set in parameter 4-56 Warning Feedback Low.
The feedback is higher than the limit set in parameter 4-57 Warning Feedback High.
2-setup: All setups
Change during operation: True
Default value: 0.01 s
2-setup: All setups
Change during operation: True
AU363928304090en-000101 / 130R0982
Parameters