VLT® Flow Drive FC 111
Programming Guide
Table 327: Option:
[0]
[1]
16-62 Analog input 53
Default value: 1
Conversion index: -2
View the actual value at input 53.
Table 328: Range:
Min: 0
16-63 Terminal 54 Setting
Default value: [0] Current mode
Conversion index: -
View the setting of input terminal 54.
Table 329: Option:
[0]
[1]
16-64 Analog input 54
Default value: 1
Conversion index: -2
View the actual value at input 54.
Table 330: Range:
Min: 0
16-65 Analog output 42 [mA]
Default value: 0 mA
Conversion index: -2
View the actual value at output 42 in mA. The value shown reflects the selection in parameter 6–90 Terminal 42 Mode and parameter
6-91 Terminal 42 Analog Output.
Table 331: Range:
Min: 0 mA
16-66 Digital Output
Default value: 0
Conversion index: 0
View the binary value of all digital outputs.
152 | Danfoss A/S © 2021.07
Current mode
Voltage mode
Parameter type: Range
Data type: u_int16
Max: 20
Parameter type: Option
Data type: u_int8
Current mode
Voltage mode
Parameter type: Range
Data type: u_int16
Max: 20
Parameter type: Range
Data type: u_int16
Max: 20 mA
Parameter type: Range
Data type: VisibleString
2-setup: 1 setup
Change during operation: True
Default value: 1
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: True
Default value: 1
2-setup: 1 setup
Change during operation: True
Default value: 0 mA
2-setup: 1 setup
Change during operation: True
AU363928304090en-000101 / 130R0982
Parameters