Download Print this page
Danfoss VLT Flow Drive FC 111 Design Manual
Danfoss VLT Flow Drive FC 111 Design Manual

Danfoss VLT Flow Drive FC 111 Design Manual

Hide thumbs Also See for VLT Flow Drive FC 111:

Advertisement

Quick Links

Design Guide
VLT® Flow Drive FC 111
vlt-drives.danfoss.com

Advertisement

loading
Need help?

Need help?

Do you have a question about the VLT Flow Drive FC 111 and is the answer not in the manual?

Questions and answers

Summary of Contents for Danfoss VLT Flow Drive FC 111

  • Page 1 Design Guide VLT® Flow Drive FC 111 vlt-drives.danfoss.com...
  • Page 3 Variable Air Volume 3.1.2.2 Constant Air Volume 3.1.2.3 Cooling Tower Fan 3.1.2.4 Condenser Pumps 3.1.2.5 Primary Pumps 3.1.2.6 Secondary Pumps 3.1.3 Check Valve Monitoring 3.1.4 Dry Pump Detection 3.1.5 End of Curve Detection Danfoss A/S © 2021.04 AJ363928382091en-000101/130R0983 | 3...
  • Page 4 Extreme Running Conditions 3.7.1 Introduction 3.7.2 Motor Thermal Protection (ETR) 3.7.3 Thermistor Inputs 3.7.3.1 Example with Digital Input and 10 V Power Supply 3.7.3.2 Example with Analog Input and 10 V Power Supply 4 | Danfoss A/S © 2021.04 AJ363928382091en-000101/130R0983...
  • Page 5 Relays and Terminals on Enclosure Size H6 6.4.3 Relays and Terminals on Enclosure Size H7 6.4.4 Relays and Terminals on Enclosure Size H8 6.4.5 Relays and Terminals on Enclosure Size H13–H14 View of Control Shelf Danfoss A/S © 2021.04 AJ363928382091en-000101/130R0983 | 5...
  • Page 6 Setup Wizard for Open-loop Applications 7.2.2.4 Setup Wizard for Closed-loop Applications 7.2.2.5 Motor Setup 7.2.2.6 Changes Made Function 7.2.2.7 Changing Parameter Settings 7.2.2.8 Accessing All Parameters via the Main Menu 7.2.3 Main Menu 6 | Danfoss A/S © 2021.04 AJ363928382091en-000101/130R0983...
  • Page 7 8.4.10 Parameter Value (PWE) 8.4.11 Data Types Supported by the Drive 8.4.12 Conversion 8.4.13 Process Words (PCD) Examples 8.5.1 Writing a Parameter Value 8.5.2 Reading a Parameter Value Modbus RTU 8.6.1 Prerequisite Knowledge Danfoss A/S © 2021.04 AJ363928382091en-000101/130R0983 | 7...
  • Page 8 Force/Write Single Coil (05 hex) 8.10.4 Force/Write Multiple Coils (0F hex) 8.10.5 Read Holding Registers (03 hex) 8.10.6 Preset Single Register (06 hex) 8.10.7 Preset Multiple Registers (10 hex) 8.10.8 Read/Write Multiple Registers (17 hex) 8 | Danfoss A/S © 2021.04 AJ363928382091en-000101/130R0983...
  • Page 9 VLT® Flow Drive FC 111 Design Guide Contents 8.11 Danfoss FC Control Profile 8.11.1 Control Word According to FC Profile (8-10 Protocol = FC Profile) 8.11.2 Explanation of Each Control Bit 8.11.3 Status Word According to FC Profile (STW) 8.11.4 Explanation of Each Status Bit 8.11.5...
  • Page 10 VLT® Energy Box software allows energy consumption comparisons of HVAC fans and pumps driven by Danfoss drives and alterna- tive methods of flow control. Use this tool to accurately project the costs, savings, and payback of using Danfoss drives on HVAC fans, pumps, and cooling towers.
  • Page 11 The ErP Directive is the European Ecodesign Directive for energy-related products. The directive sets ecodesign requirements for energy-related products, including drives, and aims at reducing the energy consumption and environmental impact of products by establishing minimum energy-efficiency standards. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 11...
  • Page 12 Disconnect the drive from the mains. Press [Off/Reset] on the LCP before programming parameters. Ensure that the drive is fully wired and assembled when it is connected to AC mains, DC supply, or load sharing. 12 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 13 An internal failure in the drive can result in serious injury when the drive is not properly closed. Ensure that all safety covers are in place and securely fastened before applying power. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 13...
  • Page 14 Illustration 1: Fan Curves (A, B, and C) for Reduced Fan Volumes SYSTEM CURVE FAN CURVE Volume % ENERGY CONSUMED 100 120 160 180 Volume % Illustration 2: Energy Savings with Drive Solution 14 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 15 3.1.1.3 Comparison of Energy Savings The Danfoss drive solution offers major savings compared with traditional energy saving solutions such as discharge damper solu- tion and inlet guide vanes (IGV) solution. This is because the drive is able to control fan speed according to thermal load on the system, and the drive has a built-in facility that enables the drive to function as a building management system, BMS.
  • Page 16 Illustration 5: Energy Savings Discharge dampers reduce power consumption. Inlet guide vanes offer a 40% reduction, but are expensive to install. The Danfoss drive solution reduces energy consumption with more than 50% and is easy to install. It also reduces noise, mechanical stress, and wear-and-tear, and extends the life span of the entire application.
  • Page 17 1050r pm 750r pm (kW ) shaf t 1650r pm 1350r pm 1050r pm 750r pm Illustration 7: Energy Table 5: Result Distribution Valve regulation Drive control Hours Power Consumption Power Consumption Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 17...
  • Page 18 Use the VLT® Energy Box software that is introduced in chapter Additional Resources to calculate the cost savings that can be ach- ieved by using a drive. 18 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 19 P.F.C Factor 0/10V Correction Mains Mains Mains Illustration 9: Traditional Fan System without a Drive D.D.C. Direct digital control Sensor Pressure E.M.S. Energy management system Sensor Temperature V.A.V. Variable air volume Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 19...
  • Page 20 Centrifugal devices such as fans behave according to the centrifugal laws. This means that the fans decrease the pressure and flow they produce as their speed is reduced. Their power consumption is thereby significantly reduced. The PI controller of the drive can be used to eliminate the need for additional controllers. 20 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 21 Several features of the Danfoss dedicated drive can be utilized to improve the performance of the CAV system. One concern of controlling a ventilation system is poor air quality. The programmable minimum frequency can be set to maintain a minimum amount of supply air regardless of the feedback or reference signal.
  • Page 22 Several features of the Danfoss dedicated drive can be utilized to improve the performance of cooling tower fans applications. As the cooling tower fans drop below a certain speed, the effect the fan has on cooling the water becomes small. Also, when utilizing a gearbox to frequency control the tower fan, a minimum speed of 40–50% is required.
  • Page 23 Using a drive instead of a throttling valve simply saves the energy that would have been absorbed by the valve. This can amount to savings of 15–20% or more. Trimming the pump impeller is irreversible, thus if the conditions change and higher flow is required the impeller must be replaced. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 23...
  • Page 24 If the flow rate needs to be increased later in the sys- tem’s life, the drive can simply increase the pump speed instead of requiring a new pump impeller. 24 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 25 N O T I C E When running multiple pumps in parallel, they must run at the same speed to maximize energy savings, either with individual dedicated drives or 1 drive running multiple pumps in parallel. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 25...
  • Page 26 3.2 Control Structures 3.2.1 Introduction There are two control modes for the drive: • Open loop. • Closed loop. Select [0] Open loop or [1] Closed loop in parameter 1-00 Configuration Mode. 26 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 27 PM motors (permanent magnet motors) in IEC standard enclosure sizes operated by Danfoss drives. The commissioning procedure is comparable to the existing one for asynchronous (induction) motors by utilizing the Danfoss VVC PM control strategy.
  • Page 28 See the following illustration. Ref. signal Ref. P 20-01 Desired FB conversion flow Flow Flow signal Illustration 20: Feedback Signal Conversion 3.2.7 Reference Handling Details for open-loop and closed-loop operation. 28 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 29 20-93 PI Proportional Gain and parameter 20-94 PI Integral Time. However, sometimes it may be helpful to optimize these parameter values to provide faster system response while still controlling speed overshoot. 3.2.9 Adjusting the Manual PI Procedure Start the motor. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 29...
  • Page 30 43.6 50.2 53.8 63.7 71.5 67.5 (75 kW (100 hp) 71.5 dB) 73.5 The values are measured under the background of 35 dBA noise and the fan running with full speed. 30 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 31 5 MHz. Since the leakage current (I ) is carried back to the unit through the shield ), there is only a small electromagnetic field (I ) from the shielded motor cable according to the following illustration. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 31...
  • Page 32 Drives installed in the second environment with a supply voltage equal to or above 1000 No limit line. Make V or rated current equal to or above 400 A or intended for use in complex systems. an EMC plan. 32 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 33 3x380– 480 V IP20 H3 RFI filter (EN55011 A1/B, EN/IEC 61800-3 C2/C1) 30–90 kW – – 50 (164) – 20 (66) – – – (40–125 hp) 3x380– 480 V IP20 Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 33...
  • Page 34 The total voltage distortion THDv is calculated based on the individual voltage harmonics us- ing this formula:   +  U   +  ...  +  U THD % = U % of U) 3.4.4.1 Harmonics Emission Requirements Equipment is connected to the public supply network. 34 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 35 Actual 30 kW (40 hp), IP20, 380–480 V (typical) 36.7 13.8 Limit for R ≥120 Harmonic current distortion factor (%) THDi PWHD Actual 30 kW (40 hp), 380–480 V (typical) 40.6 28.8 Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 35...
  • Page 36 Table 18: Harmonic Current 30–90 kW (40–120 hp), 380-480 V Individual harmonic current I Actual 30–90 kW (40–120 hp), IP20, 380-480 V (typical) 36.7 13.8 Limit for R ≥120 Harmonic current distortion factor (%) 36 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 37 The immunity requirements for drives depend on the environment in which they are installed. The requirements for the industrial environment are higher than the requirements for the home and office environment. All Danfoss drives comply with the require- ments for the industrial environment and therefore comply also with the lower requirements for home and office environment with a large safety margin.
  • Page 38 C A U T I O N INSTALLATION AT HIGH ALTITUDE At altitudes above 2000 m (6500 ft), contact Danfoss regarding PELV. 3.6 Ground Leakage Current Follow national and local codes regarding protective earthing of equipment where leakage current exceeds 3.5 mA.
  • Page 39 Illustration 28: Influence of Line Distortion on Leakage Current If the leakage current exceeds 3.5 mA, compliance with EN/IEC 61800-5-1 (power drive system product standard) requires special care. Reinforce grounding with the following protective earth connection requirements: Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 39...
  • Page 40 50 Hz 150 Hz Frequency Mains harmonics Cable Illustration 29: Mains Contributions to Leakage Current The amount of leakage current detected by the RCD depends on the cut-off frequency of the RCD. 40 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 41 The control unit may attempt to correct the ramp if parameter 2-17 Over-voltage Control is enabled. The drive turns off to protect the transistors and the DC-link capacitors when a certain voltage level is reached. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 41...
  • Page 42 3.7.2 Motor Thermal Protection (ETR) Danfoss uses ETR to protect the motor from being overheated. It is an electronic feature that simulates a bimetal relay based on internal measurements. The characteristic is shown in the following illustration.
  • Page 43 >2.9 κΩ Illustration 33: Digital Input/10 V Power Supply 3.7.3.2 Example with Analog Input and 10 V Power Supply The drive trips when the motor temperature is too high. Parameter set-up: Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 43...
  • Page 44 <800⇒2.9 k N O T I C E Make sure that the selected supply voltage follows the specification of the used thermistor element. ETR is activated in parameter 1-90 Motor Thermal Protection. 44 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 45 AX: No A options B options 31–32 BX: No B options C0 options MCO 33–34 CX: No C options C1 options X: No C1 options C option software 36–37 XX: No options Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 45...
  • Page 46 RS485 4.2.2 IP21 Enclosure Kit IP21 is an optional enclosure element available for IP20 units. If the enclosure kit is used, an IP20 unit is upgraded to comply with enclosure IP21. 46 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 47 VLT® Flow Drive FC 111 Design Guide Selection and Ordering Illustration 36: H1–H5 Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 47...
  • Page 48 IP20 90 (120) 943 (37.1) 390 (15.3) 335 (13.2) 132B0219 4.2.3 Decoupling Plate Use the decoupling plate for EMC-correct installation. The following illustration shows the decoupling plate on an H3 enclosure. 48 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 49 Table 25: Options and Accessories Enclo- sure size H1 [kW H2 [kW H3 [kW H4 [kW H5 [kW H8 [kW H6 [kW (hp)] H7 [kW (hp)] Mains (hp)] (hp)] (hp)] (hp)] (hp)] (hp)] volt- Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 49...
  • Page 50 Drive input cur- Default switching THDi level [%] Order number filter Code number filter rent continuous frequency [kHz] IP00 IP20 22 (30) 41.5 130B1274 130B1111 30 (40) 130B1275 130B1176 37 (50) 130B1291 130B1201 50 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 51 C2 (EN 55011 A1), or 20 m (65.6 ft) according to EN/IEC 61800-3 C1(EN 55011 B) can be achieved. Table 30: RFI Filters - Details Power Type Torque Weight Ordering [Nm (in- [kg (lb)] Number (hp)] lb)] Size 380– 480 V Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 51...
  • Page 52 0.8 (1.8) 132B0245 (4.0–10) (6.2– 7.1) 11–15 FN3258-30-47 10.6 1.9–2.2 1.2 (2.6) 132B0246 (15–20) (16.8– 19.5) 18.5–22 FN3258-42-47 10.6 1.9–2.2 1.4 (3.1) 132B0247 (25–30) (16.8– 19.5) Illustration 39: RFI Filter - Dimensions 52 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 53 18.5–22 30–45 55–75 (25–30) (40–60) (70–100) Height [mm (in)] 334 (13.1) 518 (20.4) 550 (21.7) 660 (26) 402 (15.8) 595 (23.4)/635 (25), 45 kW 630 (24.8)/690 (27.2), 75 kW 800 (31.5) Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 53...
  • Page 54 17 (0.67) 17 (0.67) Maximum weight kg (lb) 9.5 (20.9) 24.5 (54) 36 (79) 51 (112) Including decoupling plate. Illustration 41: Dimensions, Enclosure Sizes H13–H14 Front view Back view Side view 54 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 55 100 (4) IP20 5.5–7.5 (7.5–10) 100 (4) IP20 11–15 (15–20) 100 (4) IP20 18.5–22 (25–30) 100 (4) IP20 30–45 (40–60) 200 (7.9) IP20 55–75 (70–100) 200 (7.9) IP20 90 (125) 225 (8.9) Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 55...
  • Page 56 One or more door fans are required on the enclosure to remove heat not contained in the back channel of the drive. The fans also remove any additional losses generated by other components inside the drive. 56 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 57 To guard against injury, wear personal protective equipment such as gloves, safety glasses, and safety shoes. Always lift the drive using the dedicated eye bolts at the top of the drive. See the following illustration. 65° Illustration 42: Lifting the Drive Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 57...
  • Page 58 Slide the lower fastener slots in the drive over the M10 bolts. Tip the drive against the wall, and secure the top with 2 M10 bolts in the mounting holes. Example Illustration 43: Drive-to-wall Mounting Holes Top mounting holes Lower fastener slots 58 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 59 5.3.6.1 Airflow for H13 & H14 Enclosures 225 mm (8.9 in) 225 mm (8.9 in) Illustration 45: Standard Airflow Configuration for Enclosures H13 and H14 Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 59...
  • Page 60 5.4.3 Derating for Low Air Pressure and High Altitudes The cooling capability of air is decreased at low air pressure. For altitudes above 2000 m (6562 ft), contact Danfoss regarding PELV. Below 1000 m (3281 ft) altitude, derating is not necessary. For altitudes above 1000 m (3281 ft), decrease the ambient temperature or the maximum output current.
  • Page 61 45 C 113 F 。 。 [ kHz ] 50 C 122 F [kHz] 18.5–22 kW (25–30 hp), 400 V, Enclosure Size H5, IP20 30–37 kW (40–50 hp), 400 V, Enclosure Size H6, IP20 Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 61...
  • Page 62 55 ˚C (131 ˚F) 110–315 kW (150–450 hp), 400 V, Enclosure Size H13–H14, 110–315 kW (150–450 hp), 400 V, Enclosure Size H13–H14, IP20, Switching Pattern 60 AVM IP20, Switching Pattern SFAVM 62 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 63 All wiring must comply with local and national regulations regarding cross-section and ambient temperature requirements. • Power connection wire recommendation: Minimum 75 °C (167 °F) rated copper wire. 9.2.4 Cable Length and Cross-section for recommended wire sizes and types. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 63...
  • Page 64 Avoid installation with twisted shield ends (pigtails), because it reduces the shielding effect at high frequencies. Use the cable clamps provided. • Ensure the same potential between the drive and the ground potential of PLC. • Use star washers and galvanically conductive installation plates. 64 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 65 Motor cable Minimum 200 mm (7.87 in) between control Mains-supply cable, mains cable, and between mains motor cable Motor, 3 phases and Reinforced protective earth protective earth Illustration 47: EMC-compliant Installation Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 65...
  • Page 66 Considerations 6.4 Relays and Terminals 6.4.1 Relays and Terminals on Enclosure Sizes H1–H5 -DC +DC Illustration 48: Enclosure Sizes H1–H5 IP20, 380–480 V, 0.37–22 kW (0.5–30 hp) Mains Motor Ground Relays 66 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 67 Illustration 49: Enclosure Size H6 IP20, 380–480 V, 30–45 kW (40–60 hp) Mains Ground Motor Relays 6.4.3 Relays and Terminals on Enclosure Size H7 Illustration 50: Enclosure Size H7 IP20, 380–480 V, 55–75 kW (70–100 hp) Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 67...
  • Page 68 Design Guide Considerations Mains Ground Relays Motor 6.4.4 Relays and Terminals on Enclosure Size H8 Illustration 51: Enclosure Size H8 IP20, 380–480 V, 90 kW (125 hp) Mains Ground Relays Motor 68 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 69 6.5 View of Control Shelf The control shelf of H13-H14 drives holds the keypad, known as the local control panel or LCP. The control shelf also includes the control terminals, relays, and various connectors. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 69...
  • Page 70 0.5 (4) IP20 18.5–22 (25–30) 1.2 (11) 1.2 (11) 1.2 (11) 0.5 (4) 0.8 (7) 0.5 (4) IP20 30–45 (40–60) 4.5 (40) 4.5 (40) – 0.5 (4) 3 (27) 0.5 (4) 70 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 71 For 380–480 V, 110–315 kW (150–450 hp) units, if the drive is supplied from an isolated mains source (IT mains, floating delta, or grounded delta) or TT/TN-S mains with grounded leg, the RFI switch is recommended to be turned off via parameter 14-50 RFI Filter Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 71...
  • Page 72 IEC 61800-3. If optimum EMC performance is needed, or parallel motors are connected, or the motor cable length is above 25 m (82 ft), Danfoss recommends setting parameter 14-50 RFI Filter to [On]. It is important to use isolation monitors that are rated for use together with power electronics (IEC 61557-8).
  • Page 73 6.9.2 Short-circuit Protection Danfoss recommends using the fuses and circuit breakers listed in this chapter to protect service personnel or other equipment in case of an internal failure in the unit or a short circuit on the DC link. The drive provides full short-circuit protection in case of a short circuit on the motor.
  • Page 74 75 (100) Moeller NZMB1- A200 gG-200 90 (125) Moeller NZMB2- A250 gG-250 110 (150) – aR-315 132 (175) – aR-350 160 (250) – aR-400 200 (300) – aR-500 250 (350) – aR-630 74 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 75 Use a flat-edged screwdriver to push down the lock lever of the terminal cover under the LCP, then remove the terminal cover as shown in Illustration Illustration 55: Removing the Terminal Cover H13-H14 Press the tips of the cradle cover inwards as shown in Illustration 56, and then lift the cradle cover up. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 75...
  • Page 76 Calculate the efficiency of the drive (η ) at different loads based on the following illustration. Multiply the factor in the following illustration by the specific efficiency factor listed in the specification tables. 76 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 77 To avoid the premature aging of motors that are not designed to be used with drives, such as those motors without phase insula- tion paper or other insulation reinforcement, Danfoss strongly recommends a dU/dt filter or a sine-wave filter fitted on the out- put of the drive.
  • Page 78 5 (16) 0.132 0.88 5.220 25 (82) 0.172 1.026 4.772 50 (164) 0.222 1.00 3.603 400 V 22 kW (30 hp) 5 (16) 0.132 0.88 5.220 25 (82) 0.172 1.026 4.772 78 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 79 1.14 1.267 10 (33) 1.22 3.253 50 (164) 0.38 2.526 100 (328) 0.56 1.16 1.657 150 (492) 0.74 1.16 1.254 400 V 55 kW (74 hp) 10 (33) 0.46 1.12 1.948 Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 79...
  • Page 80 30 (98) – – – 150 (492) 0.66 1418 1725 300 (984) 0.96 1530 1277 200–315 (300–450) 30 (98) – – – 150 (492) 0.56 1261 1820 300 (984) 0.78 1278 1295 80 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 81 Motor direction is shown to the bottom left of the display – indicated by a small arrow pointing either clockwise or counter- clockwise. The triangle indicates if the LCP is in Status, Quick Menu, or Main Menu. B. Menu key Press [Menu] to select among Status, Quick Menu, or Main Menu. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 81...
  • Page 82 Use the Quick Menu to program the most common functions. The Quick Menu consists of: • Wizard for open-loop applications. • Wizard for closed-loop applications. • Motor set-up. • Changes made. 82 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 83 A OUT / D OUT Illustration 60: Drive Wiring The wizard can always be accessed again through the quick menu. Press [OK] to start the wizard. Press [Back] to return to the status view. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 83...
  • Page 84 (Do not AMA) Do AMA ... the Wizard starts Auto Motor Adapt OK AMA running AMA Failed Press OK ----- AMA OK AMA Failed Illustration 61: Setup Wizard for Open-loop Applications 84 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 85 Parameter 1-46 Position Detection Gain. • Parameter 1-48 Current at Min Inductance for d-axis. • Parameter 1-49 Current at Min Inductance for q-axis. • Parameter 1-66 Min. Current at Low Speed. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 85...
  • Page 86 Parameter 1-30 Stator Resist- ance (Rs) Parameter 1-37 0.000–1000.000 mH Size related Enter the value of the d-axis inductance. Obtain the value d-axis Induc- from the permanent magnet motor datasheet. tance (Ld) 86 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 87 The minimum reference is the lowest value obtainable by Parameter 3-02 Minimum Refer- summing all references. ence Parameter 3-03 -4999.000–4999.000 The maximum reference is the lowest obtainable by sum- ming all references. Maximum Ref- erence Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 87...
  • Page 88 [0] Current Terminal 53 [1] Voltage mode Parameter [0] Off – [0] Off 30-22 Locked [1] On Rotor Detection 0.05–1 s – Parameter 0.10 s 30-23 Locked Rotor Detection Time [s] 88 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 89 00.50 6-25 T54 high Feedback 6-25 T54 high Feedback 0050 20-94 PI integral time 0050 0020.00 1-29 Automatic Motor Adaption ... the Wizard starts Illustration 62: Setup Wizard for Closed-loop Applications Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 89...
  • Page 90 Parameter 1-39 Motor Poles. • Parameter 1-40 Back EMF at 1000 RPM. • Parameter 1-44 d-axis Inductance Sat. (LdSat). • Parameter 1-45 q-axis Inductance Sat. (LqSat). • Parameter 1-46 Position Detection Gain. 90 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 91 Changing this parameter affects the settings of other pa- rameters. Parameter 1-29 – Performing an AMA optimizes motor performance. Automatic Mo- tor Adaption (AMA) Parameter 1-30 0.000–9999.000 Ω Size related Set the stator resistance value. Stator Resist- ance (Rs) Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 91...
  • Page 92 When PM is selected, [1] Enabled this parameter is enabled. -4999.000–4999.000 The minimum reference is the lowest value obtainable by Parameter 3-02 summing all references. Minimum Refer- ence 92 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 93 6-21 Terminal 54 High Voltage/pa- High Ref./ rameter 6-23 Terminal 54 High Current. Feedb. Value Parameter 6-26 0.00–10.00 s 0.01 Enter the filter time constant. Terminal 54 Fil- ter Time Con- stant Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 93...
  • Page 94 [121] 440–480 V/60 Hz/Delta [122] 440–480 V/60 Hz Parameter 1-10 [0] Asynchron *[0] Asynchron Setting the parameter value might change these parame- Motor Con- ters: [1] PM, non-salient SPM struction [3] PM, salient IPM 94 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 95 Parameter 2-10 Brake Function. • Parameter 4-14 Motor Speed High Limit [Hz]. • Parameter 4-19 Max Output Frequency. • Parameter 4-58 Missing Motor Phase Function. • Parameter 14-65 Speed Derate Dead Time Compensation. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 95...
  • Page 96 Lq. Ideally, this parameter has the same value as parameter tance Sat. 1-38 q-axis Inductance (Lq). However, if the motor supplier (LqSat) provides an induction curve, enter the induction value, which is 200% of the nominal current. 96 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 97 [1] On Rotor Detection 0.05–1.00 s – Parameter 0.10 s 30-23 Locked Rotor Detection Time [s] 7.2.2.6 Changes Made Function The changes made function lists all parameters changed from default settings. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 97...
  • Page 98 Select [1] All to LCP. Press [OK]. 7.3.2 Transferring Data from the LCP to the Drive Procedure Go to parameter 0-50 LCP Copy. Press [OK]. Select [2] All from LCP. Press [OK]. 98 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 99 • Parameter 15-05 Over Volt's • Parameter 15-30 Alarm Log: Error Code • Parameter group 15-4* Drive identification • Parameter 18-10 FireMode Log:Event 7.5.2 Two-finger Initialization Procedure Power off the drive. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 99...
  • Page 100 • Parameter 15-00 Operating hours • Parameter 15-03 Power Up's • Parameter 15-04 Over Temp's • Parameter 15-05 Over Volt's • Parameter group 15-4* Drive identification • Parameter 18-10 FireMode Log:Event 100 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 101 To prevent impedance mismatch, use the same type of cable throughout the entire network. When connecting a motor to the drive, always use shielded motor cable. Table 49: Cable Specifications Cable Shielded twisted pair (STP) Impedance [Ω] Cable length [m (ft)] Maximum 1200 (3937) (including drop lines). Maximum 500 (1640) station-to-station. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 101...
  • Page 102 To terminate the RS485 bus, use the terminator switch on the main control board of the drive. Illustration 65: Terminator Switch Factory Setting The factory setting for the switch is OFF. 102 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 103 The default selection depends on the protocol selected in parameter 8-30 Protocol. 8.1.5 EMC Precautions To achieve interference-free operation of the RS485 network, Danfoss recommends the following EMC precautions. N O T I C E Observe relevant national and local regulations, for example regarding protective earth connection. Failure to ground the cables properly can result in communication degradation and equipment damage.
  • Page 104 8.2 FC Protocol 8.2.1 Overview The FC protocol, also referred to as FC bus or standard bus, is the Danfoss standard fieldbus. It defines an access technique accord- ing to the master/follower principle for communications via a fieldbus. One master and a maximum of 126 followers can be connected to the bus. The master selects the individual followers via an ad- dress character in the telegram.
  • Page 105 8.4.3 Telegram Length (LGE) The telegram length is the number of data bytes plus the address byte ADR and the data control byte BCC. Table 52: Length of Telegrams 4 data bytes LGE=4+1+1=6 bytes Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 105...
  • Page 106 PWE high PCD1 PCD2 Illustration 70: Parameter Block Text block The text block is used to read or write texts via the data block. PCD1 PCD2 Illustration 71: Text Block 106 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 107 Write parameter value in RAM and EEPROM (word). Read text. Table 54: Response Response follower->master Bit number Response No response. Parameter value transferred (word). Parameter value transferred (double word). Command cannot be performed. Text transferred. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 107...
  • Page 108 PWE block contains no value. To change a parameter value (write), write the new value in the PWE block and send from the master to the follower. 108 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 109 100. A conversion factor of 0.1 means that the value transferred is multiplied by 0.1. The value 100 is thus perceived as 10.0. Table 57: Conversion Conversion index Conversion factor 3600 0.01 0.001 0.0001 Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 109...
  • Page 110 Read the value in parameter 3-41 Ramp 1 Ramp Up Time. PKE = 1155 hex - Read parameter value in parameter 3-41 Ramp 1 Ramp Up Time: • IND = 0000 hex. • = 0000 hex. HIGH • = 0000 hex. 110 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 111 8.6 Modbus RTU 8.6.1 Prerequisite Knowledge Danfoss assumes that the installed controller supports the interfaces in this manual, and strictly observes all requirements and limi- tations stipulated in the controller and drive. The built-in Modbus RTU (remote terminal unit) is designed to communicate with any controller that supports the interfaces de- fined in this manual.
  • Page 112 • 1 bit for even/odd parity; no bit for no parity. • 1 stop bit if parity is used; 2 bits if no parity. Error check field Cyclic redundancy check (CRC). 112 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 113 CRC during receipt of the telegram and compares the calculated value to the actual value received in the CRC field. 2 unequal values result in bus timeout. The error-checking field contains a 16-bit binary value implemented as 2 8-bit bytes. After the Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 113...
  • Page 114 DC brake No DC brake Coast stop No coast stop Quick stop No quick stop Freeze frequency No freeze frequency Ramp stop Start No reset Reset No jog Ramp 1 Ramp 2 114 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 115 Reserved for legacy drives VLT® 5000 and VLT® 2800. 40002 Reserved – Reserved for legacy drives VLT® 5000 and VLT® 2800. 40003 Reserved – Reserved for legacy drives VLT® 5000 and VLT® 2800. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 115...
  • Page 116 N O T I C E The status word and main actual value is always sent in the list from the drive to the controller. 116 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 117 Function code (hex) Read coils Read holding registers Write single coil Write single register Write multiple coils Write multiple registers Get comm. event counter Report follower ID Read write multiple registers Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 117...
  • Page 118 8.9.2 Storage of Data The coil 65 decimal determines whether data written to the drive is stored in EEPROM and RAM (coil 65 = 1), or only in RAM (coil 65 = 0). 118 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 119 1 data byte contains the coil addressed in the query. The other coils follow toward the high-order end of this byte, and from low order to high order in subsequent bytes. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 119...
  • Page 120 The normal response is an echo of the query, returned after the coil state has been forced. Table 73: Response Field name Example (hex) Follower address Function Force data HI Force data LO 120 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 121 Follower address 01 (drive address) Function 0F (write multiple coils) Coil address HI Coil address LO 10 (coil address 17) Quantity of coils HI Quantity of coils LO 10 (16 coils) Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 121...
  • Page 122 The query telegram specifies the register reference to be preset. Register addresses start at 0, that is, register 1 is addressed as 0. Example: Write to parameter 1-00 Configuration Mode, register 1000. 122 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 123 Table 80: Query Field name Example (hex) Follower address Function Starting address HI Starting address LO Number of registers HI Number of registers LO Byte count Write data HI (Register 4: 1049) Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 123...
  • Page 124 02 (Parameter 3-03 Maximum Reference is 32 bits long, that is, 2 registers) Write starting address HI 04 (Register address 1239) Write starting address LO D7 (Register address 1239) Quantity to write HI Quantity to write LO 124 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 125 Read registers value LO Read registers value HI Read registers value LO Error check (CRC) – 8.11 Danfoss FC Control Profile 8.11.1 Control Word According to FC Profile (8-10 Protocol = FC Profile) Master-follower Speed ref. no.: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0...
  • Page 126 In parameter 8-50 Coasting Select, define how bit 03 gates with the corresponding function on a digital input. 8.11.2.4 Bit 04, Quick Stop Bit 04 = 0: Makes the motor speed ramp down to stop (set in parameter 3-81 Quick Stop Ramp Time). 126 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 127 Use bit 13 to select from the 2 set-ups according to the following table. The function is only possible when [9] Multi set-ups is selected in parameter 0-10 Active Set-up. Table 86: Set-up selection Setup Bit 13 Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 127...
  • Page 128 Bit 00=0: The drive trips. Bit 00=1: The drive controls are ready but the power component does not necessarily receive any supply (if there is 24 V external supply to controls). 128 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 129 Bit 12=1: The drive stops because of overtemperature but the unit does not trip and resumes operation once the overtemperature normalizes. 8.11.4.14 Bit 13, Voltage OK/Limit Exceeded Bit 13=0: There are no voltage warnings. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 129...
  • Page 130 Reverse Forward (1) -max- +max Par.3-03 Par.3-03 Max reference Max reference 100% (0hex) (4000hex) Par.3-00 set to Forward (0) min-max Par.3-02 Par.3-03 Max reference Min reference Illustration 81: Reference and MAV 130 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 131 Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to Danfoss MyDrive®...
  • Page 132 Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to Danfoss MyDrive®...
  • Page 133 If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to Danfoss MyDrive® ecoSmart website.
  • Page 134 Parameter 16-61 Terminal 53 Setting: 1 = voltage, 0 = current Terminal 54 mode Parameter 16-63 Terminal 54 Setting: 1 = voltage, 0 = current Voltage level 0–10 V Input resistance, R Approximately 10 kΩ 134 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 135 Maximum terminal load (AC-1) on 01–02/04–05 (NO) (Resistive 250 V AC, 3 A load) Maximum terminal load (AC-15) on 01–02/04–05 (NO) (Induc- 250 V AC, 0.2 A tive load @ cosφ 0.4) Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 135...
  • Page 136 EN/IEC 61800-5-1 EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3 EMC standards, Immunity EN 61800-3, EN 61000-3-12, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6 136 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 137 Determined according to EN 50598-2 at: • Rated load. • 90% rated frequency. • Switching frequency factory setting. • Switching pattern factory setting. For more information on derating, see chapter Derating. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 137...
  • Page 138 Nominal motor current Maximum output current VLT,MAX Rated output current supplied by the drive VLT,N Kilogram Kilohertz Local control panel Meter Millihenry inductance Milliampere Millisecond Minute Motion control tool Nanofarad Newton meter 138 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 139 Torque generated on the output shaft and speed from 0 RPM to maximum speed on the motor. Motor frequency when the jog function is activated (via digital terminals or bus). Motor frequency. Maximum motor frequency. Minimum motor frequency. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 139...
  • Page 140 A start-disable command belonging to the control commands in group 1. See the table in chapter Input for more details. Stop command A stop command belonging to the control commands in group 1. See the table in chapter Input for more details. 140 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 141 The numerical local control panel interface for control and programming of the drive. The display is numerical and the panel is used to show process values. The NLCP has storing and copy functions. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 141...
  • Page 142 The drive compensates for the motor slip by giving the frequency a supplement that follows the measured motor load, keeping the motor speed almost constant. Smart logic control (SLC) The SLC is a sequence of user-defined actions executed when the smart logic controller evaluates the associated user-defined events as true. 142 | Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983...
  • Page 143 ) improves the dynamics and stability, both when the speed reference is changed and in relation to the load torque. 60° AVM Refer to the switching pattern 60° asynchronous vector modulation. Danfoss A/S © 2021.04 AJ363928382091en-000101 / 130R0983 | 143...
  • Page 144 Conversion....................109 Feedback conversion.................. 28 Conversion factor..................109 Flow meter......................24 Conversion index..................109 Force/write multiple coil (0F hex)............121 Cooling......................56 Force/write single coil (05 hex).............120 Cooling tower fan..................22 Freeze output....................139 CT mode......................60 Function Codes...................117 144 | Danfoss A/S © 2021.04 AJ363928382091en-000101/130R0983...
  • Page 145 Purpose of the manual................10 PWE......................... 108 Main menu......................98 Mains drop-out....................42 Mains supply....................133 Qualified personnel..................12 Manual derating................... 60 Quick menu....................82 Manual PI adjustment.................29 Quick transfer....................98 MCT 10 setup software................10, 81 Menu key......................81 Danfoss A/S © 2021.04 AJ363928382091en-000101/130R0983 | 145...
  • Page 146 Status menu....................82 Wire size......................73 Status word....................128 Wiring schematic..................64 Switching frequency Wizard Use with RCDs..................40 Open-loop application..............82 Switching on the output................41 Closed-loop application..............82 Symbols......................12 Motor set-up..................82 Synchronous motor speed..............140 Telegram length..................105 146 | Danfoss A/S © 2021.04 AJ363928382091en-000101/130R0983...
  • Page 147 VLT® Flow Drive FC 111 Design Guide Index Danfoss A/S © 2021.04 AJ363928382091en-000101/130R0983 | 147...
  • Page 148 Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.