Change during operation: True Using ETR (electronic thermal relay), the motor temperature is calculated based on frequency, current, and time. Danfoss recom- mends using the ETR function, if a thermistor is not present. The functionality is the same for asynchronous motors and PM motors.
Page 199
Cause An internal fault occurs. Troubleshooting Contact your Danfoss supplier. 5.5.18 ALARM 44, Earth Fault II Cause There is a discharge from the output phases to ground, either in the cable between the drive and the motor or in the motor itself.
Page 201
The control card and power card are incompatible. Troubleshooting • To check compatibility, contact the Danfoss supplier with the type code from the unit nameplate and the part numbers on the cards. 5.5.34 ALARM 79, Illegal Power Section Configuration Cause Internal fault.
See the fire mode data in the alarm log. 5.5.47 ALARM 250, New Spare Part Cause The power or switch mode supply has been exchanged. Troubleshooting • Contact the local Danfoss supplier. 5.5.48 ALARM 251, New Type Code Cause The drive has a new type code. Troubleshooting •...
Page 214
Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.