Danfoss VLT Flow Drive FC 111 Programming Manual page 49

Hide thumbs Also See for VLT Flow Drive FC 111:
Table of Contents

Advertisement

VLT® Flow Drive FC 111
Programming Guide
1-30 Stator Resistance (Rs)
Default value: Configuration dependent
Conversion index: -3
Set the stator resistance value. Enter the value from a motor datasheet or perform an AMA on a cold motor.
Table 54: Range:
Min: 0.0 Ohm
Max: 9999.000 Ohm
1-31 Rotor Resistance (Rr)
Default value: Configuration dependent
Conversion index: -3
Enter the rotor resistance value. Obtain the value from a motor data sheet or by performing an AMA on a cold motor. The default
setting is calculated by the drive from motor nameplate data.
Table 55: Range:
Min: 0
Max: 9999.000 Ohm
1-33 Stator Leakage Reactance (X1)
Default value: Configuration dependent
Conversion index: -3
Set the stator leakage reactance value. Enter the value from a motor data sheet or perform an AMA on a cold motor. The default
setting is calculated by the drive from motor nameplate data.
Table 56: Range:
Min: 0.0 Ohm
Max: 9999.000 Ohm
1-35 Main Reactance (Xh)
Default value: Configuration dependent
Conversion index: -2
Set the main reactance value. Enter the value from a motor data sheet or perform an AMA on a cold motor. The default setting is
calculated by the drive from motor nameplate data.
Table 57: Range:
Min: 0.0 Ohm
Max: 9999.00 Ohm
1-37 d-axis Inductance (Ld)
Default value: Configuration dependent
Conversion index: -3
Enter the value of the d-axis inductance. Obtain the value from the permanent magnet motor data sheet or perform an AMA on a
cold motor.
Table 58: Range:
Min: 0.001 mH
Danfoss A/S © 2021.07
Parameter type: Range
Data type: u_int32
Parameter type: Range
Data type: u_int32
Default value: Configuration dependent
Parameter type: Range
Data type: u_int32
Parameter type: Range
Data type: u_int32
Parameter type: Range
Data type: int32
Max: 65535 mH
2-setup: All setups
Change during operation: False
Default value: Configuration dependent
2-setup: All setups
Change during operation: False
2-setup: All setups
Change during operation: False
Default value: Configuration dependent
2-setup: All setups
Change during operation: False
Default value: Configuration dependent
2-setup: All setups
Change during operation: False
Default value: Configuration dependent
Parameters
AU363928304090en-000101 / 130R0982 | 49