Danfoss VLT Flow Drive FC 111 Programming Manual page 95

Hide thumbs Also See for VLT Flow Drive FC 111:
Table of Contents

Advertisement

VLT® Flow Drive FC 111
Programming Guide
Table 164: Range:
Min: 0 mA
6-23 Terminal 54 High Current
Default value: 20 mA
Conversion index: -2
Enter the high current value corresponding to the high reference/feedback set in parameter 6-25 Terminal 54 High Ref./Feedb. Value.
Table 165: Range:
Min: 0 mA
6-24 Terminal 54 Low Ref./Feedb. Value
Default value: 0
Conversion index: -3
Enter the reference or feedback value that corresponds to the voltage or current set in parameter 6-20 Terminal 54 Low Voltage to
parameter 6-22 Terminal 54 Low Current.
Table 166: Range:
Min: -4999
6-25 Terminal 54 High Ref./Feedb. Value
Default value: Configuration dependent
Conversion index: -3
Enter the reference or feedback value that corresponds to the voltage or current set in parameter 6-21 Terminal 53 High Voltage to
parameter 6-23 Terminal 53 High Current.
Table 167: Range:
Min: -4999
Max: 4999
6-26 Terminal 54 Filter Time Constant
Default value: 0.01 s
Conversion index: -2
Enter the time constant. This constant is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal
54. A high time constant value improves dampening, but also increases the time delay through the filter.
Table 168: Range:
Min: 0.01 s
6-29 Terminal 54 mode
Default value: [1] Voltage mode
Conversion index: -
Select whether terminal 54 is used for current or voltage input.
Danfoss A/S © 2021.07
Max: 20 mA
Parameter type: Range
Data type: u_int16
Max: 20 mA
Parameter type: Range
Data type: int32
Max: 4999
Parameter type: Range
Data type: int32
Default value: Configuration dependent
Parameter type: Range
Data type: u_int16
Max: 10 s
Parameter type: Option
Data type: u_int8
Default value: 4 mA
2-setup: All setups
Change during operation: True
Default value: 20 mA
2-setup: All setups
Change during operation: True
Default value: 0
2-setup: All setups
Change during operation: True
2-setup: All setups
Change during operation: True
Default value: 0.01 s
2-setup: 1 setup
Change during operation: True
AU363928304090en-000101 / 130R0982 | 95