VLT® Flow Drive FC 111
Programming Guide
13-00 SL Controller Mode
Default value: [0] Off
Conversion index: -
To enable the smart logic control to start when a start command is present, for example, via a digital input, Select [1] On. To disable
the smart logic control, select [0] Off.
Table 218: Option:
[0]
Off
[1]
On
13-01 Start Event
Default value: [39] Start command
Conversion index: -
To activate smart logic control, select the boolean (True or False) input.
Table 219: Option:
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
116 | Danfoss A/S © 2021.07
Parameter type: Option
Data type: u_int8
Disable the smart logic controller.
Enable the smart logic controller.
Parameter type: Option
Data type: u_int8
Enter the fixed value False in the logic rule.
Enter the fixed value True in the logic rule.
The motor runs.
The motor runs within programmed current ranges (parameter 4-50 Warning Current Low and pa-
rameter 4-51 Warning Current High).
The motor runs at reference speed.
The motor current is outside the range set in parameter 4-18 Current Limit.
The motor current is lower than set in parameter 4-50 Warning Current Low.
The motor current is higher than set in parameter 4-51 Warning Current High.
The thermal warning turns on when the temperature exceeds the limit in the motor, the drive, or
the thermistor.
Mains phase loss warning or alarm, if parameter 14-12 Function at Mains Imbalance is not set at [2]
Disabled.
The drive reverses.
A warning is present.
An alarm is present.
A trip lock alarm is present.
Use the result of comparator 0 in the logic rule.
Use the result of comparator 1 in the logic rule.
Use the result of comparator 2 in the logic rule.
Use the result of comparator 3 in the logic rule.
Use the result of logic rule 0 in the logic rule.
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: True
AU363928304090en-000101 / 130R0982
Parameters