The maximum motor frequency. Danfoss technical literature is available in electronic form on the documentation CD that is shipped with the product, or in print from your local Danfoss sales office. The minimum motor frequency. MCT 10 Set-up Software support The rated motor frequency (nameplate data).
Table 3.1 The Laws of Proportionality 3.1.4 Comparison of Energy Savings VLT Solution The Danfoss frequency converter solution offers major savings compared with traditional energy saving solutions such as discharge damper solution and inlet guide vanes (IGV) solution. This is because the frequency converter is...
(AHUs) with a heating coil, and many are also used to air Several features of the Danfoss HVAC dedicated frequency condition buildings and have a cooling coil. Fan coil units converter can be utilized to improve the performance of are frequently used to assist in the heating and cooling the CAV system.
Product Overview Design Guide 3.1.16 Cooling Tower Fan Several features of the Danfoss HVAC dedicated frequency converter can be utilized to improve the performance of cooling tower fans applications. As the cooling tower fans Cooling tower fans cool condenser-water in water-cooled drop below a certain speed, the effect the fan has on chiller systems.
3.2.2 PM/EC+ Motor Control • Support only complete AMA of the stator resistance Rs in the system. The Danfoss EC+ concept provides the possibility for using • No stall detection (supported from software high-efficient PM motors (permanent magnet motors) in version 2.80).
A short circuit between 2 output phases causes an INSTALLATION AT HIGH ALTITUDE overcurrent in the inverter. The inverter is turned off At altitudes above 2000 m (6500 ft), contact Danfoss individually when the short circuit current exceeds the regarding PELV.
(Ω) to coast. 3.7.1 Motor Thermal Protection (ETR) 4000 Danfoss uses ETR to protect the motor from being 3000 overheated. It is an electronic feature that simulates a bimetal relay based on internal measurements. The charac- 1330 teristic is shown in Illustration 3.56.
H 0000 H 03E8 7.6.1 Introduction high Illustration 7.10 Telegram Danfoss assumes that the installed controller supports the interfaces in this document, and strictly observes all requirements and limitations stipulated in the controller NOTICE and frequency converter. Parameter 4-14 Motor Speed High Limit [Hz] is a single...
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
Page 109
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
Page 110
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
Page 111
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
Circuit breakers must be designed for protection in a Short-circuit protection circuit capable of supplying a maximum of 10000 A Danfoss recommends using the fuses and circuit breakers (symmetrical), 480 V maximum. listed in Table 8.11 to protect service personnel or other...
Page 124
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.
Need help?
Do you have a question about the VLT HVAC Basic Drive FC 101 and is the answer not in the manual?
Questions and answers