Danfoss VLT Flow Drive FC 111 Programming Manual page 19

Hide thumbs Also See for VLT Flow Drive FC 111:
Table of Contents

Advertisement

VLT® Flow Drive FC 111
Programming Guide
Parameter
Range
0.18–110 kW/0.25–150 hp
Parameter 1-20
Motor Power
50–1000 V
Parameter 1-22
Motor Voltage
20–400 Hz
Parameter 1-23
Motor Frequen-
cy
Parameter 1-24
0.01–1000.00 A
Motor Current
50–60000 RPM
Parameter 1-25
Motor Nominal
Speed
0.1–10000.0 Nm
Parameter 1-26
Motor Cont.
Rated Torque
Parameter 1-29
Automatic Mo-
tor Adaption
(AMA)
Parameter 1-30
0.000–9999.000 Ω
Stator Resist-
ance (Rs)
Danfoss A/S © 2021.07
Default
Usage
Parameter 1-49 Current at Min Inductance for q-axis.
Parameter 1-66 Min. Current at Low Speed.
Parameter 1-70 PM Start Mode.
Parameter 1-72 Start Function.
Parameter 1-73 Flying Start.
Parameter 1-80 Function at Stop.
Parameter 1-82 Min Speed for Function at Stop [Hz].
Parameter 1-90 Motor Thermal Protection.
Parameter 2-00 DC Hold/Motor Preheat Current.
Parameter 2-01 DC Brake Current.
Parameter 2-02 DC Braking Time.
Parameter 2-04 DC Brake Cut In Speed.
Parameter 2-10 Brake Function.
Parameter 4-14 Motor Speed High Limit [Hz].
Parameter 4-19 Max Output Frequency.
Parameter 4-58 Missing Motor Phase Function.
Parameter 14-65 Speed Derate Dead Time Compensation.
Size related
Enter the motor power from the nameplate data.
Size related
Enter the motor voltage from the nameplate data.
Size related
Enter the motor frequency from the nameplate data.
Size related
Enter the motor current from the nameplate data.
Size related
Enter the motor nominal speed from the nameplate data.
Size related
This parameter is available when parameter 1-10 Motor Con-
struction is set to options that enable permanent motor
mode.
Changing this parameter affects the settings of other pa-
rameters.
Off
Performing an AMA optimizes motor performance.
Size related
Set the stator resistance value.
Programming
N O T I C E
AU363928304090en-000101 / 130R0982 | 19