VLT® Flow Drive FC 111
Programming Guide
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[97]
Check Valve Monitor
[160]
No alarm
[161]
Running reverse
[165]
Local ref. active
[166]
Remote ref. active
[167]
Start command activ
[168]
Drive in hand mode
[169]
Drive in auto mode
[188]
AHF Capacitor Con-
nect
[190]
No-Flow
[191]
Dry Pump
[192]
End Of Curve
[193]
Sleep Mode
[194]
Broken Belt Function
[196]
Fire Mode
[198]
Drive Bypass
[211]
Cascade Pump 1
[212]
Cascade Pump 2
88 | Danfoss A/S © 2021.07
See parameter 13-52 SL Controller Action. The input goes high whenever the smart logic action
[38] Set dig. out. A high is executed. The input goes low whenever the smart logic [32] Action Set
dig. out. A low is executed.
See parameter 13-52 SL Controller Action. The input goes high whenever the smart logic action
[39] Set dig. out. B high is executed. The input goes low whenever the smart logic [33] Action Set
dig. out. B low is executed.
See parameter 13-52 SL Controller Action. The input goes high whenever the smart logic action
[40] Set dig. out. C high is executed. The input goes low whenever the smart logic [34] Action Set
dig. out. C low is executed.
See parameter 13-52 SL Controller Action. The input goes high whenever the smart logic action
[41] Set dig. out. D high is executed. The input goes low whenever the smart logic [35] Action Set
dig. out. D low is executed.
A check valve monitor condition has been detected. Enable the function in parameter 22-04
Check Valve Monitor.
The output is high when no alarm is present.
The output is high when the drive is running counterclockwise (the logical product of the status
bits running and reverse).
The output is high when local reference is activated by the [Hand On] key on the LCP or by hand-
on command of digital input.
The output is high when remote reference is activated by the [Auto On] key on the LCP or by
auto-on command of digital input.
The output is high when there is an active start command (that is, via digital input bus connec-
tion or [Hand On] or [Auto On], and no stop command is active.
The output is high when the drive is in hand-on mode (as indicated by the LED light above
[Hand On]).
The output is high when the drive is in auto-on mode (as indicated by the LED light above [Auto
On]).
Connect or disconnect AHF capacitor.
A no-flow condition has been detected. See parameter group 22-2* No-Flow Detection.
A dry-pump condition has been detected. Enable the function in parameter 22-26 Dry Pump
Function.
An end-of-curve condition has been detected. Enable the function in parameter 22-50 End of
Curve Function.
The drive/system has entered sleep mode. See parameter group 22-4* Sleep Mode.
A broken-belt condition has been detected. Enable the function in parameter 22-60 Broken Belt
Function.
The drive is operating in fire mode. See parameter group 24-0* Fire Mode.
To be used as a signal for activating an external electromechanical bypass, switching the motor
directly on line. See parameter group 24-1* Drive Bypass.
Cascade pump 1 is running.
Cascade pump 2 is running.
Parameters