VLT® Flow Drive FC 111
Programming Guide
Table 169: Option:
[0]
[1]
4.8.4 6-7* Analog/Digital Output 45
Parameters for configuring the scaling and limits for analog/digital output terminal 45. Analog outputs are current outputs: 0/4–
20 mA. Resolution on analog output is 12 bit. Analog output terminals can also be set up as digital output.
6-70 Terminal 45 Mode
Default value: [0] 0-20 mA
Conversion index: -
Set terminal 45 to act as analog output or as digital output.
Table 170: Option:
[0]
[1]
[2]
6-71 Terminal 45 Analog Output
Default value: [0] No operation
Conversion index: -
Select the function of terminal 45 as an analog current output. See also parameter 6-70 Terminal 45 Mode.
Table 171: Option:
[0]
[100]
[101]
[102]
[103]
[106]
[139]
[254]
6-72 Terminal 45 Digital Output
Default value: [0] No operation
Conversion index: -
Select the function of terminal 45 as a digital current output. See also parameter 6-70 Terminal 45 Mode. See parameter 5-40 Function
Relay for description of the options.
Table 172: Option:
[0]
No operation
[1]
Control Ready
96 | Danfoss A/S © 2021.07
Current mode
Voltage mode
Parameter type: Option
Data type: u_int8
0-20 mA
4-20 mA
Digital Output
Parameter type: Option
Data type: u_int8
No operation
Output frequency
Reference
Feedback
Motor Current
Power
Bus Control
DC Link Voltage
Parameter type: Option
Data type: u_int8
2-setup: All setups
Change during operation: True
2-setup: All setups
Change during operation: True
2-setup: All setups
Change during operation: True
AU363928304090en-000101 / 130R0982
Parameters