VLT® Flow Drive FC 111
Programming Guide
Table 133: Selected Multi Fire Mode Preset Reference (Parameter 24-08 Mul FM Preset Reference)
Selected multi fire mode preset reference:
Fire mode preset reference 0
Fire mode preset reference 1
Fire mode preset reference 2
Fire mode preset reference 3
Fire mode preset reference 4
Fire mode preset reference 5
Fire mode preset reference 6
Fire mode preset reference 7
5-10 Terminal 18 Digital Input
Default value: [8] Start
Conversion index: -
Parameter for configuring the input function on input terminal 18.
Table 134: Option:
[0]
No operation
No reaction to signals transmitted to the terminal.
[1]
Reset
Reset the drive after a trip/alarm. Trip lock alarms can be reset.
[2]
Coast inverse
Leave the motor in free mode. Logic 0⇒coast stop.
[3]
Coast and reset
Reset and coast stop inverted input (NC). Leaves the motor in free mode and resets the drive. Logic
inverse
0⇒coast stop and reset.
[4]
Quick stop in-
Inverted input (NC). Generates a stop in accordance with the quick-stop ramp time set in parameter
verse
3-81 Quick Stop Ramp Time. After ramping down, the shaft is in free mode.
[5]
DC-brake in-
Inverted input for DC braking (NC). Stops the motor by energizing it with DC current for a certain time
verse
period, see parameter 2-01 DC Brake Current. The function is only active when the value in parameter
2-02 DC Braking Time is different from 0. This selection is not possible when parameter 1-10 Motor Con-
struction is set to [1] PM non-salient SPM.
[6]
Stop inverse
The stop inverse function generates the stop function when the selected terminal goes from logical
level 1 to 0 (not latched). Stop is performed according to selected ramp time.
[7]
External Inter-
Same function as coast stop, inverse, but external interlock generates the alarm message external fault
lock
on the display when the terminal programmed for coast inverse is logic 0. If programmed for external
interlock, the alarm message is also active via digital outputs and relay outputs. If the cause for the
external interlock is removed, the alarm can be reset using a digital input, fieldbus, or the [Reset] key.
[8]
Start
Select start for a start/stop command. Logic 1 = start, logic 0 = stop. (Default digital input 18).
[9]
Latched start
If a pulse is applied for a minimum of 2 ms, the motor starts. The motor stops when stop inverse is
activated.
[10]
Reversing
Change direction of motor shaft rotation. The reversing signal only changes the direction of rotation, it
does not activate the start function. Select [2] Both directions in parameter 4-10 Motor Speed Direction. 0
= normal, 1 = reversing.
70 | Danfoss A/S © 2021.07
Fire mode reference bit
2
0
0
0
0
1
1
1
1
Parameter type: Option
Data type: u_int8
Fire mode reference bit
1
0
0
1
1
0
0
1
1
2-setup: All setups
Change during operation: True
AU363928304090en-000101 / 130R0982
Parameters
Fire mode reference bit
0
0
1
0
1
0
1
0
1