Programming Guide
15-06 Reset kWh Counter
Default value: [0] Do not reset
Conversion index: -
Table 271: Option:
[0]
Do not reset
Do not reset.
[1]
Reset counter
Select this option and press [OK] to reset the kWh counter to 0 (see parameter 15-02 kWh Counter).
15-07 Reset Running Hours Counter
Default value: [0] Do not reset
Conversion index: -
Table 272: Option:
[0]
Do not reset
Do not reset.
[1]
Reset counter
Select this option and press [OK] to reset the running hours counter to 0 (see parameter 15-01 Running
Hours).
4.12.2 15-3* Alarm Log
Parameters in this group are array parameters, where up to 10 fault logs can be viewed. [0] is the most recent logged data, and [9]
the oldest. Fault codes, values, and time stamp can be viewed for all logged data.
15-30 Alarm Log: Error Code
Default value: 0
Conversion index: 0
View the fault code and lookup its meaning in chapter Troubleshooting.
Table 273: Range:
Min: 0
15-31 InternalFaultReason
Default value: 0
Conversion index: 0
View a description of the error. This parameter is used with alarm 38, Internal Fault.
Table 274: Range:
Min: -32767
15-32 Alarm Log: Time
Default value: 0 s
Conversion index: 0
View the time when the logged event occurred. Time is measured in seconds from the drive start-up.
Table 275: Range:
Min: 0 s
Max: 2147483647
140 | Danfoss A/S © 2021.07
Parameter type: Option
Data type: u_int8
Parameter type: Option
Data type: u_int8
Parameter type: Range
Data type: u_int16
Max: 255
Parameter type: Range
Data type: int16
Max: 32767
Parameter type: Range
Data type: u_int32
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: True
Default value: 0
2-setup: 1 setup
Change during operation: True
Default value: 0
2-setup: All setups
Change during operation: False
Default value: 0 s
AU363928304090en-000101 / 130R0982
Parameters

Advertisement

Table of Contents
loading

Table of Contents